IOL-Error Type Designation acc. to IO-
Link Spec.
Meaning
0x1000
COM_ERR
Communication error
Possible source: the addressed port is parameterized
as digital input DI and is not in IO-Link mode
0x1100
I_SERVICE_TIMEOUT
Timeout in communication, device does not respond
in time
0x5600
M_ISDU_CHECKSUM
Master reports checksum error, access to device not
possible
0x5700
M_ISDU_ILLEGAL
Device can not respond to master request
0x8000
APP_DEV
Application error in the device
0x8011
IDX_NOTAVAIL
Index not available
0x8012
SUBIDX_NOTAVAIL
Sub-Index not available
0x8020
SERV_NOTAVAIL
The service is temporarily not available.
0x8021
SERV_NOTA-
VAIL_LOCCTRL
Service temporarily not available, device is busy (e. g.
teaching or parameterization of the device via the
master active)
0x8022
SERV_NOTAVAIL_DEVC-
TRL
Service temporarily not available, device is busy (e. g.
teaching or parameterization of the device via DTM/
PLC etc. active)
0x8023
IDX_NOT_WRITEABLE
Access denied, Index cannot be written
0x8030
PAR_VALOUTOFRNG
Parameter value out of the valid range
0x8031
PAR_VALGTLIM
Parameter value above the upper limit
0x8032
PAR_VALLTLIM
Parameter value value below the lower limit
0x8033
VAL_LENOVRRUN
Length of data to be written does not match the
length defined for this parameter
0x8034
VAL_LENUNDRUN
0x8035
FUNC_NOTAVAIL
Function not available in the device
0x8036
FUNC_UNAVAILTEMP
Function temporarily unavailable in the device
0x8040
PARA_SETINVALID
Invalid parameter: Parameters not consistent with
other parameters in the device.
0x8041
PARA_SETINCONSIST
Inconsistent parameters
0x8082
APP_DEVNOTRDY
Application not ready, device busy
0x8100
UNSPECIFIC
Vendor specific, according to device documentation
0x8101…
0x8FF
VENDOR_SPECIFIC