Configuring interfaces to the central BMS
BACnet MS/TP interface
Single room control system FSL
‑
CONTROL II
61
PICS_X-AIRCONTROL_v1.0.doc
- 5 -
Binary Value Objects
Property
Remark / Value
RW
Object_Identifier
binary-value, instance 1 … 20
R
Object_Name
R
Object_Type
BINARY_VALUE (5)
R
Present_Value
INACTIVE (0, Initial) / ACTIVE (1)
Status_Flags
IN_ALARM:
0
FAULT:
0
OVERRIDDEN:
0
OUT_OF_SERVICE: 0
R
Event_State
NORMAL (0)
R
Out_Of_Service
FALSE (0)
R
Inactive_Text
R
Active_Text
R
R: Read Property, W: Write Property, COVU: Unsolicited Change of Value Notification
Instance
Object_Name
Inactive_Text
Active_Text
Present_Value
1
“StartPCM”
“Off”
“On”
RW
2
“Fire”
“Normal”
“Fire”
RW
3
“Window”
“Close”
“Open”
RW
4
“ExtraTime”
“Inactive”
“Active”
RW
5
“ActExtraTime”
“Inactive”
“Active”
R
6
“ActWindow”
“Close”
“Open”
R
7
“FAlarm”
“Normal”
“Frostalarm”
R
COVU
8
“Alarm1”
“Normal”
“Alarm1”
R
COVU
9
“Alarm2”
“Normal”
“Alarm2”
R
COVU
10
“Release”
“Off”
“On”
R
11
“Status_PowerSupply”
“Normal”
“LowPower”
R
COVU
12
“Status_EMFSLIO”
“Normal”
“ComFail”
R
COVU
13
“Status_Fan”
“Normal”
“FanBlocked”
R
COVU
14
“Status_Sensor”
“Normal”
“SensorFail”
R
COVU
15
“Status_Filter”
“Normal”
“FilterAlarm”
R
COVU
16
“Status_FlowControl”
“Normal”
“FlowAlarm”
R
COVU
17
“Status_Damper”
“Normal”
“CalibrationFail”
R
COVU
18
“ActFire”
“Normal”
“Fire”
R
19
“FanForce”
“Inactive”
“Active”
RW
20
“ActFanForce”
“Inactive”
“Active”
R