He, 21 March 2017
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
13
nvoSetPtOffset
SNVT_temp_p
Function: Feedback of a temperature offset to the central BMS
LON value
BACnet value
Modbus value
(Register 24)
Enter as follows 3K
3
Enter as follows 3K
3
Enter without decimal
places, multiply with 100,
e.g. 3K
3
Invalid: 327,67
Invalid: 327,67
Invalid: 327,67
nvoRoomTemp / ActRoomTemp
SNVT_temp_p
Function: Feedback of the room air actual temperature to the central BMS
LON value
BACnet value
Modbus value
(Register 25)
Enter with 2 decimal
places, e.g. 23 °C
23.00
Enter with 2 decimal
places, e.g. 23 °C
23.00
Enter without decimal
places, multiply with 100,
e.g. 23.00 °C
2300
Invalid: 327,67
Invalid: 327,67
Invalid: 327,67
nvoRelHumid / ActRelHumid
SNVT_lev_percent
Function: Feedback of the actual relative humidity in the room to the central BMS
(additional hardware required, or default setting by the central BMS)
LON value
BACnet value
Modbus value
(Register 26)
-163.840….+163.830
0….100%
0….100%
Invalid: +163,830
Invalid: 65535
Invalid: 65535
Configuring interfaces to the central BMS
List of data points
Single room control system FSL
‑
CONTROL II
53