nviRelHumid
SNVT_lev_percent
Function: Default setting of relative room air humidity
LON value
BACnet value
Modbus value
(Register 7)
-163.840….+163.830
0….100%
0….100%
Invalid: +163,830
Invalid: 65535
Invalid: 65535
nviVOC_Room
SNVT_ppm
Function: Default setting of room VOC value
LON value
BACnet value
Modbus value
(Register 9)
0….65535
0….65535
0….65535
Invalid: 65535
Invalid: 65535
Invalid: 65535
nviVOC_Outside
SNVT_ppm
Function: Default setting of outdoor air VOC value
LON value
BACnet value
Modbus value
(Register 10)
0….65535
0….65535
0….65535
Invalid: 65535
Invalid: 65535
Invalid: 65535
nviFire
SNVT_hvac_emerg
Function: Emergency switch-off of fire protection
LON value
Identifier
BACnet
value
Modbus
value
(Register 11)
Description
0
emerg_normal
0
0
No switch-off
5
emerg_fire
1
1
Switch-off
Configuring interfaces to the central BMS
List of data points
Single room control system FSL
‑
CONTROL II