Configuring interfaces to the central BMS
BACnet MS/TP interface
Single room control system FSL
‑
CONTROL II
60
PICS_X-AIRCONTROL_v1.0.doc
- 4 -
Analog Value Objects
Property
Remark / Value
RW
Object_Identifier
analog-value, instance 1 … 18
R
Object_Name
R
Object_Type
ANALOG_VALUE (2)
R
Present_Value
Status_Flags
IN_ALARM:
0
FAULT:
0
OVERRIDDEN:
0
OUT_OF_SERVICE: 0
R
Event_State
NORMAL (0)
R
Out_Of_Service
FALSE (0)
R
Units
R
R: Read Property, W: Write Property
Instance
Object_Name
Units
Initial Present_Value Present_Value
1
“OutsideTemp”
degrees-Celsius (62)
327.67
RW
2
“ActOutsideTemp”
degrees-Celsius (62)
327.67
R
3
“RoomTemp_Set”
degrees-Celsius (62)
327.67
RW
4
“SetptOffset”
degrees-Celsius (62)
327.67
R
5
“TempOffset”
degrees-Celsius (62)
327.67
RW
6
“RoomTemp”
degrees-Celsius (62)
327.67
RW
7
“ActRoomTemp”
degrees-Celsius (62)
327.67
R
8
“RelHumid”
percent-relative-humidity (29)
0
RW
9
“ActRelHumid”
percent-relative-humidity (29)
0
R
10
“VOC_Room”
parts-per-million (96)
0
RW
11
“ActVOC_Room”
parts-per-million (96)
0
R
12
“VOC_Outside”
parts-per-million (96)
0
RW
13
“DischAirTemp”
degrees-Celsius (62)
327.67
R
14
“EffectSetpt”
degrees-Celsius (62)
327.67
R
15
“RTemp”
degrees-Celsius (62)
327.67
R
16
“Sum_Sup”
liters-per-second (87)
0
R
17
“Sum_Exh”
liters-per-second (87)
0
R
18
“SystemDevices”
no-units (95)
0
R