4.6.2 Suspending fire dampers installed remote from solid walls and ceiling slabs
Fig. 35: Dry mortarless installation with installation kit WE
1
FKA2-EU
2.6
Installation kit WE, see
2.19
Joint filler (Promat
®
filler, Promat
®
ready-to-use
filler or mineral wool,
≥
1000 °C,
≥
80 kg/m³ or
mortar according to installation and operating
manual)
8.19
Overlay PROMATECT®-LS, d = 35 mm
9.4
Sheet steel duct with fire-rated cladding and sus-
pension system according to Promat® manual,
construction 478, latest edition
9.5
Suspension system (by others) consisting of:
a
Threaded rod
M10: B
×
H
≤
800
×
200 mm
M12: B
×
H
≤
1000
×
600 mm
M12#: B
×
H > 1000
×
600 mm
b
Hilti
®
mounting rail MQ 41
×
3 mm or equivalent
c
Hilti
®
drilled plate MQZ L13 or equivalent
days
Hexagon nut with washer
#
Damper sizes > 1000
×
600 mm require two sus-
pension points underneath the fire damper at a
distance of 150 mm from each other
to EI 90 S (horizontal installation position)
Installation
Fixing the fire damper > Suspending fire dampers installed remote from solid walls and ceiling slabs
Fire damper Type FKA2-EU
51