Installation positions
The fire damper may be installed so that the damper
blade shaft is horizontal or vertical. The position of the
release mechanism is not critical but the mechanism
must remain accessible for maintenance (take applica-
tion-specific restrictions into account).
Fig. 11: Blade shaft horizontal or vertical
a
Minimum distance between two fire dampers.
Unless specified otherwise in the respective installa-
tion description, the installation is carried out in sep-
arate installation openings. The distance between
two fire dampers is
≥
200 mm.
The fire damper with assembled duct smoke detector
must be installed in a horizontal installation position,
duct smoke detector at the top, (deviations on request).
Fig. 12: Horizontal installation
Installation
General installation information
Fire damper Type FKA2-EU
29