background image

Electric shower

4

E-002-A

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 
protection must conform with BS 7671 (IEE 
wiring regulations) and be sufficient for the 
amperage required.
The following notes are for guidance only:

1

 

The shower must only be connected to a 
230-240V ac supply. If you are installing a 
shower with a kilowatt rating above 9kW, it 
is advisable to contact the local electricity 
supply company.

1.1

  The electrical rating of the shower is shown 

on the rating label 

(Fig.3)

 within the unit.

2

 

 Before making any sort of electrical 
connection within the installation make sure 
that no terminal is live. If in any doubt, 
switch off the whole installation at the mains 
supply and remove the correct fuse.

3

 

The shower must be connected to its own 
independent electrical circuit. IT MUST NOT 
be connected to a ring main, spur, socket 
outlet, lighting circuit or cooker circuit.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

 

Check your consumer unit (main fuse box) 
has a main switch rating of 80A or above 
and that it has a spare fuse way which will 
take the fuse or Miniature Circuit Breaker 
(MCB) necessary for the shower 

(Fig.4).

4.1

  If your consumer unit has a rating below 

80A or if there is no spare fuse way, then the 
installation will not be straightforward and 
may require a new consumer unit serving 
the house or just the shower.

4.2

  You will need to contact the local electricity 

company. They will check the supply and 
carry out what is necessary. 

5

 

For close circuit protection DO NOT use a 
rewireable fuse. Instead use a suitably rated 
Miniature Circuit Breaker (MCB) or cartridge 
fuse 

(see Table A).

5.1

  A 30mA residual current device (RCD) must 

be installed in all UK electric and pumped 
shower circuits. This may be part of the 
consumer unit or a separate unit.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

  The switch must be accessible and clearly 

identifiable, but out of reach of a person 
using a fixed bath or shower, except for the 
cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily 
accessible to switch off after using the 
shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B).

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the 

disconnection time and thermal constraints 
which means that for any given combination 
of current demand, voltage drop and cable 
size, there is a maximum permissible circuit 
length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed in 
areas where the ambient temperature is 
above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

 

In the majority of installations, the cable 
will unavoidably be placed in one or more 
of the above conditions. This being so, it 
is strongly recommended to use a 
minimum of 10mm cabling throughout 
the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Meter

Incoming

supply

fuse

Meter

tails

Consumer

unit

Pull cord

isolating switch

Shower

unit

Fuse or

MCB

RCD

(can be part of

consumer unit)

80A or 100A

main switch

Shepperton Park,

Triton Road, Nuneaton,

Warwickshire, CV11 4NR

Table A

MCB

30/32A

32A
40A
40A
40A

40/45A

45A

cartridge

fuse

30A
35A
35A
45A
45A
45A
45A

unit 

rating

7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW

10.5kW

CIRCUIT PROTECTION

Fig.4

 Schematic of installation circuit

Fig.3

W-006-A

WARNING!

THIS APPLIANCE MUST BE EARTHED

Summary of Contents for Enlight 2

Page 1: ...Installers please note these instructions are to be left with the user 2180817B May 2012 Installation and operating instructions Enlight 2 electric shower...

Page 2: ...acing the cover 12 Commissioning 13 Operating the shower 14 Operating functions 16 Instructions for installers and service engineers only 17 Spare parts 18 Fault finding 19 20 Water Cable entry points...

Page 3: ...ill result in higher temperatures and could also cause the PRD Pressure Relief Device in the unit to operate 1 9 This product is not suitable for mounting into steam rooms or steam cubicles 2 PLUMBING...

Page 4: ...n which determines the water temperature The slower the flow the hotter the water becomes the faster the flow the cooler the water b During winter the mains water supply will be cooler than in the sum...

Page 5: ...alve 10 Guide pockets 11 Can and element assembly 12 Thermal cut out main 13 Earth connection 14 Pressure relief device 15 Outlet temperature limiter 16 Power neon 17 Trimplate Inside cover fig 2 18 C...

Page 6: ...e way which will take the fuse or Miniature Circuit Breaker MCB necessary for the shower Fig 4 4 1 If your consumer unit has a rating below 80A or if there is no spare fuse way then the installation w...

Page 7: ...current carrying capacity of the cable must be at least that of the shower circuit protection see Table B 8 1 To obtain full advantage of the power provided by the shower use the shortest cable route...

Page 8: ...all models the maximum static pressure must not exceed 1000kPa 10 bar Note If the stated flow rates are not available it may not be possible to achieve the best performance from the unit throughout th...

Page 9: ...NOT operate the shower with a damaged or kinked shower hose or a blocked showerhead which can cause the PRD to operate When commissioning the showerhead must be removed from the flexible hose while at...

Page 10: ...itions for the mains water are from the bottom or from the rear Cable entry is via the top or rear Note Deviations from the designated entry points will invalidate product approvals If bottom surface...

Page 11: ...he site for the shower use the backplate as a template and mark the two fixing holes fig 12 Drill and plug the wall An appropriate drill bit should be used If the wall is brick plasterboard or a soft...

Page 12: ...of the shower flush out the pipework to remove all swarf and system debris This can be achieved by connecting a hose to the pipework and turning on the mains water supply long enough to clear the deb...

Page 13: ...can result in cable overheating Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The supply cable must be secured either...

Page 14: ...ck the power selector is in the STOP position and the temperature control is in the 10 position Offer the cover to the unit Plug the power neon located on the backplate onto the bracket inside the cov...

Page 15: ...erate Turn on the electric and mains water supplies to the shower Rotate the power selector to COLD fig 21 and wait until water starts to flow from the flexible hose Slowly turn the temperature contro...

Page 16: ...symbol is the ECONOMY setting for using less energy when the ambient mains water temperature is high during warmer months To adjust the temperature at this setting use the temperature control Note If...

Page 17: ...re increasing the water temperature and is indicated by higher numbers Note It is advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under...

Page 18: ...Temperature limiter During normal operation if an overheat temperature is sensed power to the elements will be reduced although water will continue to flow When the temperature has cooled sufficientl...

Page 19: ...r to maintain the performance of the shower It is essential that this operation is carried out by an installer or service engineer IMPORTANT Before servicing switch off both the electricity supply and...

Page 20: ...ly 3 Thermal cut out 22011180 4 Heater can assembly 8 5kW P12120701 9 5kW P12120702 5 Stabiliser valve solenoid P12120806 assembly 6 PRD O ring 82800450 7 Inlet pipe assembly S12721002 8 Backplate Bla...

Page 21: ...ck if stop taps are fully open Check if blockage in inlet filter 2 3 1 Switch to economy power setting and readjust flow rate to give required temperature 3 1 1 See Water too hot causes 2 1 2 2 and 2...

Page 22: ...4 4 1 Have unit checked by suitably qualified electrician or contact Customer Service 5 1 1 Wait until the water pressure resumes to normal 6 1 1 Clean sprayplate and then fit a new PRD 6 2 1 Check fo...

Page 23: ...gistered with the Environment Agency under the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9659...

Page 24: ...ting of the product together with the date of purchase and where applicable details of the particular fault 2 If required the Customer Service Advisor will arrange for a qualified engineer to call 3 A...

Reviews: