background image

Electric shower

11

2

3

4

5

6

9

8

L

N

E

inlet

outlet

1

3

8

7

ELECTRICAL CONNECTIONS

SWITCH OFF THE ELECTRICITY SUPPLY AT 
THE MAINS.

Fig.13

 shows a schematic wiring diagram.

The cable entry points are shown in 

fig.1

. The 

cable can be surface clipped, hidden or via 
20mm conduit.

Note:

 Conduit entry can only be from rear. 

Route the cable into the shower unit and 
connect to the terminal block 

(fig.14)

 as 

follows:

Earth cable to terminal marked 

 E  

 

Neutral cable to terminal marked  

N

Live cable to terminal marked

  L

IMPORTANT:

 Fully tighten the terminal 

block screws and make sure that no cable 
insulation is trapped under the screws. Loose 
connections can result in cable overheating.

Note: 

The supply cable earth conductor must 

be sleeved. The outer sheath of the supply cable 
must be stripped back to the minimum.
The supply cable must be secured either by 
routing through conduit or in trunking or by 
embedding in the wall, in accordance with 
current IEE regulations.

 

The use of connections within the unit, or other 
points in the shower circuit, to supply power to 
other equipment i.e. extractor fans, pumps etc. 
will invalidate the guarantee.

DO NOT switch on the electricity supply until 
the cover has been fitted.

Note:

 The elements on UK models are to 240V 

specification and will give a lower kW rating if 
the voltage supply is below 240V.

Fig.14

Fig.13

1.

  Terminal block

2.

 Microswitch

3.

 Microswitches

4.

  Solenoid valve

5.

  Thermal cut-out (main)

6.

  Thermal cut-out 

 (outlet)

7.

 Neon

8.

 Element

9.

  Earth post

Summary of Contents for Enlight 2

Page 1: ...Installers please note these instructions are to be left with the user 2180817B May 2012 Installation and operating instructions Enlight 2 electric shower...

Page 2: ...acing the cover 12 Commissioning 13 Operating the shower 14 Operating functions 16 Instructions for installers and service engineers only 17 Spare parts 18 Fault finding 19 20 Water Cable entry points...

Page 3: ...ill result in higher temperatures and could also cause the PRD Pressure Relief Device in the unit to operate 1 9 This product is not suitable for mounting into steam rooms or steam cubicles 2 PLUMBING...

Page 4: ...n which determines the water temperature The slower the flow the hotter the water becomes the faster the flow the cooler the water b During winter the mains water supply will be cooler than in the sum...

Page 5: ...alve 10 Guide pockets 11 Can and element assembly 12 Thermal cut out main 13 Earth connection 14 Pressure relief device 15 Outlet temperature limiter 16 Power neon 17 Trimplate Inside cover fig 2 18 C...

Page 6: ...e way which will take the fuse or Miniature Circuit Breaker MCB necessary for the shower Fig 4 4 1 If your consumer unit has a rating below 80A or if there is no spare fuse way then the installation w...

Page 7: ...current carrying capacity of the cable must be at least that of the shower circuit protection see Table B 8 1 To obtain full advantage of the power provided by the shower use the shortest cable route...

Page 8: ...all models the maximum static pressure must not exceed 1000kPa 10 bar Note If the stated flow rates are not available it may not be possible to achieve the best performance from the unit throughout th...

Page 9: ...NOT operate the shower with a damaged or kinked shower hose or a blocked showerhead which can cause the PRD to operate When commissioning the showerhead must be removed from the flexible hose while at...

Page 10: ...itions for the mains water are from the bottom or from the rear Cable entry is via the top or rear Note Deviations from the designated entry points will invalidate product approvals If bottom surface...

Page 11: ...he site for the shower use the backplate as a template and mark the two fixing holes fig 12 Drill and plug the wall An appropriate drill bit should be used If the wall is brick plasterboard or a soft...

Page 12: ...of the shower flush out the pipework to remove all swarf and system debris This can be achieved by connecting a hose to the pipework and turning on the mains water supply long enough to clear the deb...

Page 13: ...can result in cable overheating Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The supply cable must be secured either...

Page 14: ...ck the power selector is in the STOP position and the temperature control is in the 10 position Offer the cover to the unit Plug the power neon located on the backplate onto the bracket inside the cov...

Page 15: ...erate Turn on the electric and mains water supplies to the shower Rotate the power selector to COLD fig 21 and wait until water starts to flow from the flexible hose Slowly turn the temperature contro...

Page 16: ...symbol is the ECONOMY setting for using less energy when the ambient mains water temperature is high during warmer months To adjust the temperature at this setting use the temperature control Note If...

Page 17: ...re increasing the water temperature and is indicated by higher numbers Note It is advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under...

Page 18: ...Temperature limiter During normal operation if an overheat temperature is sensed power to the elements will be reduced although water will continue to flow When the temperature has cooled sufficientl...

Page 19: ...r to maintain the performance of the shower It is essential that this operation is carried out by an installer or service engineer IMPORTANT Before servicing switch off both the electricity supply and...

Page 20: ...ly 3 Thermal cut out 22011180 4 Heater can assembly 8 5kW P12120701 9 5kW P12120702 5 Stabiliser valve solenoid P12120806 assembly 6 PRD O ring 82800450 7 Inlet pipe assembly S12721002 8 Backplate Bla...

Page 21: ...ck if stop taps are fully open Check if blockage in inlet filter 2 3 1 Switch to economy power setting and readjust flow rate to give required temperature 3 1 1 See Water too hot causes 2 1 2 2 and 2...

Page 22: ...4 4 1 Have unit checked by suitably qualified electrician or contact Customer Service 5 1 1 Wait until the water pressure resumes to normal 6 1 1 Clean sprayplate and then fit a new PRD 6 2 1 Check fo...

Page 23: ...gistered with the Environment Agency under the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9659...

Page 24: ...ting of the product together with the date of purchase and where applicable details of the particular fault 2 If required the Customer Service Advisor will arrange for a qualified engineer to call 3 A...

Reviews: