UPS Location 

W

a

rnings

Install your UPS indoors, away from excess moisture or heat, conductive contaminants,

dust or direct sunlight.

For best performance, keep the indoor temperature between between 32º F and 104º F

(0º C and 40º C).

Leave adequate space around all sides of the UPS for proper ventilation.

UPS Connection 

W

arnings

Connect your UPS directly to a properly grounded 

AC power outlet. Do not plug the

UPS into itself; this will damage the UPS.

Do not modify the UPS's plug, and do not use an adapter that would eliminate the UPS’

s

ground connection.

Do not use extension cords to connect the UPS to an 

AC outlet. 

Y

our warranty will be

voided if anything other than 

T

ripp Lite sur

ge suppressors are used to connect your UPS

to an outlet.

If the UPS receives power from a motor

-powered 

AC generator

, the generator must 

provide clean, filtered, computer

-grade output.

Equipment Connection 

W

a

rnings

Do not use 

T

ripp Lite UPS Systems for life support applications in which a malfunction 

or failure of a 

T

ripp Lite UPS System could cause failure or significantly alter the 

performance of a life-support device.

Batter

y W

a

rnings

Y

our UPS does not require routine maintenance. 

There are no user

-serviceable parts

inside. Do not open your UPS for any reason.

Since batteries present a risk of electrical shock and burn from high short-circuit current,

observe proper precautions. Unplug and turn of

f the UPS before performing battery

replacement. Use tools with insulated handles, and replace the existing batteries with the

same number and type of new batteries (sealed lead-acid). Do not open the batteries. Do

not short or bridge the battery terminals with any object. 

T

ripp Lite of

fers a complete

line of UPS System Replacement Battery Cartridges (R.B.C.). 

V

isit 

T

ripp Lite on the

W

eb at www

.tripplite.com/support/battery/index.cfm to locate the specific replacement

battery for your UPS.

T

he UPS batteries are recyclable. Refer to local codes for disposal requirements, or in

the USA

only call 1-800-SA

V

-LEAD or 1-800-8-BA

TTER

Y
(1-800-8-228-8379) or 

visit www

.rbrc.com for recycling information. Do not dispose of the batteries in a fire. 

Do not operate your UPS without batteries.

SA
VE THESE 

INSTR

UCTIONS

This manual contains instructions and warnings that should be followed during the 

installation, operation and storage of all 

T

ripp Lite UPS Systems. Failure to heed these

warnings will void your warranty

.

3

2

Impor

tant Saf

ety Instructions

Quic

k Installation

Connection and Star

t-Up

Plug y

our UPS into an electrical

outlet.

Plug the UPS directly into a properly ground-

ed, 3-wire, 

AC outlet that does not share a cir-

cuit with a heavy electrical load (such as an air

conditioner

, refrigerator

, etc.).

The outlet must

have an amp rating equal to or greater than

your UPS’

s input breaker rating (see

Specifications).

Note:

Once your UPS is plugged in, the fan and all

Indicator Lights will turn ON. 

The “LINE” and

“LOAD 

ACTIVE METER” LEDs will illuminate

and the UPS will beep to indicate normal operation.

However

, power is not supplied to your UPS’

AC

outlets until the UPS is turned on.

Plug y

our equipment into y

o

ur UPS.

Y

our UPS is designed to support computer

equipment only

. Y

ou will overload your UPS

if you connect devices with high power

demands such as household appliances or

laser printers to your UPS's outlets.

T

urn y

our UPS ON:

Press the “ON/TEST” Switch 

Hold it for several seconds until you 

hear a beep

Release it

The “ON

LINE” LED will now light, and your

UPS will begin providing power to its 

AC

outlets.

Note:

If this is the first time you have plugged in

your UPS, or if your UPS has been in storage for a

prolonged period, it will need to char

ge its batteri

es

for 2-4 hours before it can support connected

equip-

ment in the event of a power failure.

SU1000XL Plug 

(NEMA 5-15)

sho

wn

1

1

2

3

2

3

SU2200XL

sho

wn

SU1000XL

sho

wn

200408112 SU1000-2200-3000XL Owner’s Manual.qxd  8/24/2004  11:08 AM  Page 2

Summary of Contents for SmartOnline SU1000XL

Page 1: ...2 Quick Installation 3 Basic Operation 5 Storage and Service 11 Specifications 12 SmartOnline Intelligent True On Line Tower UPS Systems True On Line Operation Pure Sine Wave Output Models SU1000XL SU2200XL SU3000XL Copyright 2004 Tripp Lite All rights reserved SmartOnline is a trademark of Tripp Lite Troubleshooting 9 Optional Installation 4 Español 13 Français 24 200408112 SU1000 2200 3000XL Own...

Page 2: ...ic replacement battery for your UPS The UPS batteries are recyclable Refer to local codes for disposal requirements or in the USA only call 1 800 SAV LEAD or 1 800 8 BATTERY 1 800 8 228 8379 or visit www rbrc com for recycling information Do not dispose of the batteries in a fire Do not operate your UPS without batteries SAVE THESE INSTRUCTIONS This manual contains instructions and warnings that s...

Page 3: ...will shift to battery power the ON BATT and BATT ACTIVE METER LEDs will illuminate for ten seconds Alarm Silence To silence the UPS on battery alarm press this switch and hold it until you hear a beep UPS Cold Start To use your UPS as a stand alone power source when AC power is unavailable i e during a blackout press this switch and hold it until you hear a beep The UPS will then provide bat tery ...

Page 4: ...l operation this LED will light briefly when the unit is plugged in but if an internal fault or overload occurs this light will illuminate constantly to show that connected equipment will receive filtered AC utility power but will not receive battery power during a blackout In this case contact Tripp Lite for service FAULT LED This red light will flash when your UPS detects an internal fault overh...

Page 5: ...TT Prepare for imminent UPS shutdown Condition Battery Low On BYPASS LINE LOAD OVERLOAD Reduce the load the UPS supports Condition On Bypass due to Overload On FAULT Remove the cause of the short circuit Condition Short Circuit from the UPS output Flashing FAULT Check the utility line for wiring problems Condition Wiring Fault such as reversed line and neutral or a missing ground On FAULT REPLACE ...

Page 6: ... UPS for an extended period of time fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4 6 hours If you leave your UPS batteries discharged for an extended period of time they may suffer permanent loss of capacity Before returning your UPS for service follow these steps 1 Review the installation and operation instructio...

Page 7: ...erates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications Operation of this equipment is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The user must use shielded cables and connectors with this product Any chan...

Page 8: ...te deberá proporcionar una salida de corriente limpia y filtrada del tipo uti lizado para computadoras Advertencias sobre la conexión de equipos No utilice los sistemas UPS de Tripp Lite en equipo para el soporte de la vida humana donde un fallo o mal funcionamiento podría causar anomalías o alterar significativa mente el rendimiento del dispositivo para el soporte de la vida humana No conecte sup...

Page 9: ... METER durante diez segundos Silenciar alarma Para silenciar la alarma del UPS en batería pre sione el interruptor y manténgalo presionado hasta que escuche un sonido Encendido en frío del UPS Para usar su UPS como una fuente de energía autónoma cuando no haya energía de CA disponible es decir durante un apagón presione este botón y manténgalo presionado hasta que escuche un sonido El UPS suminist...

Page 10: ...S está suministrando energía al equipo a través de la batería El UPS emitirá un sonido cada dos segundos a menos que lo silencie con el interruptor ON TEST Cuando se prende esta luz puede contro lar el nivel de carga de la batería del UPS en los LED BATT ACTIVE METER Panel posterior LED REPLACE BATT Reemplazar batería Esta luz roja se ilu minará y permanecerá fija y la alarma del UPS emitirá tres ...

Page 11: ...n las secuencias descritas a contin uación para indicar que el UPS tiene dificultades de funcionamiento Luces Encendidas Parpadeando y condición Solución Encendidas REEMPLAZAR BATERÍA Deje que el sistema del UPS se Condición Reemplazar batería cargue por lo menos 12 horas y realice una autoprueba usando el interruptor de ON Test según lo descrito en la página 22 Si la luz permanece encendida pónga...

Page 12: ...s durante el despacho No use camas de Styrofoam para embalaje Cualquier daño directo indirecto especial accidental o resultante al UPS producido durante el despacho a Tripp Lite o a un centro autorizado de servicio Tripp Lite no está cubierto por la garantía Los sistemas UPS enviados a Tripp Lite o a algún centro de servicio autorizado de Tripp Lite deben tener los cargos de transporte prepagados ...

Page 13: ... ces dispositifs Ne connectez pas de suppresseurs de surtension ou de rallonges électriques à la prise de votre système UPS De tels branchements peuvent l endommager et entraîner une annulation de sa garantie tout comme celle couvrant le suppresseur de surtension Mises en garde relatives à la batterie Votre système UPS n exige pas d entretien périodique Ne l ouvrez pas quelle que soit la raison sa...

Page 14: ...iche SU1000XL NEMA 5 15 illustrée Modèle SU2200XL illustré Modèle SU1000XL illustré Votre système UPS fonctionnera correctement sans ces connexions Connexion de port série En utilisant le câble série fourni connectez le port série de votre ordinateur à celui de votre système UPS Installez sur votre ordinateur le logiciel de surveillance ASI PowerAlert inclus sur le CD ROM qui convient au système d...

Page 15: ...tème panne de courant ou présente une tension extrêmement élevée Le système UPS alimente alors l équipement à partir de la batterie Voyants du panneau avant Exploitation de base suite Voyants du panneau avant suite VOYANT BYPASS ÉVITEMENT Ce voyant jaune s allume pour signaler que le convertisseur c c c a est désactivé et que le système UPS est en mode d évitement En cours de fonctionnement normal...

Page 16: ...le bloc batterie Tripp Lite approprié à brancher Consultez le guide de l utilisateur fourni avec le bloc batterie externe pour les instructions complètes relatives à son installation et les précautions à prendre Exploitation de base suite Panneau arrière Voyants du panneau avant suite 15 amp 120V NEMA 5 15R 20 amp 120V NEMA 5 20R 20 amp 120V NEMA L5 20R 30 amp 120V NEMA L5 30R Exploitation de base...

Page 17: ...ce élevée Dépannage Dépannage suite Voyants allumés clignotent et problème Solution Allumés FAULT BYPASS LINE DÉFAILLANCE Redémarrez le système UPS Si le ÉVITEMENT ALIMENTATION 25 problème persiste consultez le Problème En mode d évitement en raison service à la clientèle de Tripp Lite d une tension de source basse Allumés FAULT BYPASS LINE DÉFAILLANCE Assurez vous qu il y a suffisamment ÉVITEMENT...

Page 18: ... doivent être prépayés Inscrire le numéro de RMA sur le paquet Si l UPS est encore couvert par la garantie de deux ans joindre une copie de votre facture d achat Renvoyer l UPS pour réparation par un transporteur assuré à l adresse que vous a donnée le technicien de service de Tripp Lite Entreposage Entretien Spécifications La politique de Tripp Lite en est une d amélioration continue Ces spécific...

Reviews: