Tripp Lite SmartOnline SU1000XL Owner'S Manual Download Page 4

“REPLACE BA

TT” LED:

This red light will be lit and

the UPS alarm

will sound three beeps* if your UPS’

s microprocessor detects a 

battery fault or if your UPS fails the automatic self-test (after you turn

your UPS ON) and the UPS battery is less than fully char

ged. Let the

UPS char

ge for 12 hours, then perform a second self test (see p.5 for

details). If the light continues to stay on, contact 

T

ripp Lite for service.

*After the initial alarm, the UPS will beep once every hour until the pr

oblem is corr

ected.

AC Receptacles: 

These receptacles provide your con-

nected equipment

with pure sine-wave 

AC output from the

AC line during normal operation

an

d

 from battery power

during blackouts and severe brownouts. 

Power provided

at these outlets is filtered to protect connected equipment

against damaging sur

ges and line noise. Each UPS

model includes a select number of receptacles arranged

into two separate load banks (clearly indicated on the

rear panel of the UPS system). 

Using PowerAlert

Software and RS-232 communications,

power at either of

these load banks may be turned ON

and OFF remotely

without af

fecting the power output at any other recepta-

cles.

See PowerAlert Software instructions for details.

Input Cir

cuit Br

eaker

Switch:

This resettable breaker prevents high

input current from damaging the UPS or the attached load. If this

breaker trips, make sure your UPS is connected to 

AC power of the

proper voltage before resetting the circuit breaker by pushing the

breaker switch in.

Fan:

The fan cools the UPS’

s internal components. It is always on

when line power is present.

External Battery Pack Connector:

Use to connect optional 

T

ripp Lite

Battery Packs for additional runtime. Contact 

T

ripp Lite Customer

Support at (773) 869-1234 for the appropriate 

T

ripp Lite battery pack

to connect. Refer to instructions available with the Battery Pack for

complete connection information and safety warnings.

7

Basic Operation 

(contin

ued)

6

Fr
ont P

anel Indicator Lights 

contin

ued

“BYP

ASS” LED:

This yellow light will be lit when the UPS’

s

DC/AC inverter is deactivated and the UPS is in the “Bypass” mode.

During normal operation this LED will light briefly when the unit is

plugged in, but if an internal fault or overload occurs this light will

illuminate constantly to show that connected equipment will receive

filtered 

AC utility power

, but will not receive battery power during a

blackout. In this case, contact 

T

ripp Lite for service.

“F
AUL

T” LED:

This red light will flash when your UPS detects an

internal fault (overheating, overvoltages, etc.) or when it detects a

wiring fault in your wall outlet (reversed phases, missing ground,

etc.)  

The UPS will only detect wiring faults when it is plugged into

a utility outlet but not turned ON. If the light persists after restarting

the UPS, contact an electrician to check the 

AC line. 

Y

our UPS will

identify the presence of most (but not all) wiring faults.

“LOAD 

ACTIVE METER” LED:

This green light will illuminate

when your UPS is receiving 

AC power to indicate that the set of four

dual-function LEDs is displaying the load level of your UPS.

“BA

TT

ACTIVE METER” LED:

This green light will be lit when

your UPS is operating from battery power to indicate that the set of

four dual-function LEDs is displaying the battery char

ge level of your

UPS. Note: the “ON BA

TT” LED will also be illuminated. 

“OVERLOAD” LED:

This red light will be lit when your UPS’

s capaci-

ty

has been exceeded while it is in on-line operation.

The UPS alarm will

beep continuously

. Immediately 

remove overload 

until light and alarm

go of

f. If you do not immediately remove the overload,

the UPS will

transfer from on-line to bypass operation.

“BA

TT

LOW” LED:

This yellow light will be lit when your UPS’

s

battery char

ge level is low

The UPS alarm will beep until either the

battery char

ge is depleted or the batteries are adequately rechar

ged.

“ON BA

TT” LED:

This green light will be lit when 

AC line voltage

is not present and your UPS is providing your equipment with battery

power

. The UPS will also beep every two seconds, unless silenced by

the “ON/TEST” Switch. 

When this light is illuminated, you can monitor

the battery char

ge level of your UPS on the “BA

TT

ACTIVE

METER” LEDs.

Basic Operation 

(contin

ued)

Rear P

anel 

Fr
ont P

anel Indicator Lights 

contin

ued

15 amp/120V

NEMA

5-15R

20 amp/120V

NEMA

5-20R

20 amp/120V

NEMA

L5-20R

30 amp/120V

NEMA

L5-30R

200408112 SU1000-2200-3000XL Owner’s Manual.qxd  8/24/2004  11:08 AM  Page 6

Summary of Contents for SmartOnline SU1000XL

Page 1: ...2 Quick Installation 3 Basic Operation 5 Storage and Service 11 Specifications 12 SmartOnline Intelligent True On Line Tower UPS Systems True On Line Operation Pure Sine Wave Output Models SU1000XL SU2200XL SU3000XL Copyright 2004 Tripp Lite All rights reserved SmartOnline is a trademark of Tripp Lite Troubleshooting 9 Optional Installation 4 Español 13 Français 24 200408112 SU1000 2200 3000XL Own...

Page 2: ...ic replacement battery for your UPS The UPS batteries are recyclable Refer to local codes for disposal requirements or in the USA only call 1 800 SAV LEAD or 1 800 8 BATTERY 1 800 8 228 8379 or visit www rbrc com for recycling information Do not dispose of the batteries in a fire Do not operate your UPS without batteries SAVE THESE INSTRUCTIONS This manual contains instructions and warnings that s...

Page 3: ...will shift to battery power the ON BATT and BATT ACTIVE METER LEDs will illuminate for ten seconds Alarm Silence To silence the UPS on battery alarm press this switch and hold it until you hear a beep UPS Cold Start To use your UPS as a stand alone power source when AC power is unavailable i e during a blackout press this switch and hold it until you hear a beep The UPS will then provide bat tery ...

Page 4: ...l operation this LED will light briefly when the unit is plugged in but if an internal fault or overload occurs this light will illuminate constantly to show that connected equipment will receive filtered AC utility power but will not receive battery power during a blackout In this case contact Tripp Lite for service FAULT LED This red light will flash when your UPS detects an internal fault overh...

Page 5: ...TT Prepare for imminent UPS shutdown Condition Battery Low On BYPASS LINE LOAD OVERLOAD Reduce the load the UPS supports Condition On Bypass due to Overload On FAULT Remove the cause of the short circuit Condition Short Circuit from the UPS output Flashing FAULT Check the utility line for wiring problems Condition Wiring Fault such as reversed line and neutral or a missing ground On FAULT REPLACE ...

Page 6: ... UPS for an extended period of time fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4 6 hours If you leave your UPS batteries discharged for an extended period of time they may suffer permanent loss of capacity Before returning your UPS for service follow these steps 1 Review the installation and operation instructio...

Page 7: ...erates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications Operation of this equipment is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The user must use shielded cables and connectors with this product Any chan...

Page 8: ...te deberá proporcionar una salida de corriente limpia y filtrada del tipo uti lizado para computadoras Advertencias sobre la conexión de equipos No utilice los sistemas UPS de Tripp Lite en equipo para el soporte de la vida humana donde un fallo o mal funcionamiento podría causar anomalías o alterar significativa mente el rendimiento del dispositivo para el soporte de la vida humana No conecte sup...

Page 9: ... METER durante diez segundos Silenciar alarma Para silenciar la alarma del UPS en batería pre sione el interruptor y manténgalo presionado hasta que escuche un sonido Encendido en frío del UPS Para usar su UPS como una fuente de energía autónoma cuando no haya energía de CA disponible es decir durante un apagón presione este botón y manténgalo presionado hasta que escuche un sonido El UPS suminist...

Page 10: ...S está suministrando energía al equipo a través de la batería El UPS emitirá un sonido cada dos segundos a menos que lo silencie con el interruptor ON TEST Cuando se prende esta luz puede contro lar el nivel de carga de la batería del UPS en los LED BATT ACTIVE METER Panel posterior LED REPLACE BATT Reemplazar batería Esta luz roja se ilu minará y permanecerá fija y la alarma del UPS emitirá tres ...

Page 11: ...n las secuencias descritas a contin uación para indicar que el UPS tiene dificultades de funcionamiento Luces Encendidas Parpadeando y condición Solución Encendidas REEMPLAZAR BATERÍA Deje que el sistema del UPS se Condición Reemplazar batería cargue por lo menos 12 horas y realice una autoprueba usando el interruptor de ON Test según lo descrito en la página 22 Si la luz permanece encendida pónga...

Page 12: ...s durante el despacho No use camas de Styrofoam para embalaje Cualquier daño directo indirecto especial accidental o resultante al UPS producido durante el despacho a Tripp Lite o a un centro autorizado de servicio Tripp Lite no está cubierto por la garantía Los sistemas UPS enviados a Tripp Lite o a algún centro de servicio autorizado de Tripp Lite deben tener los cargos de transporte prepagados ...

Page 13: ... ces dispositifs Ne connectez pas de suppresseurs de surtension ou de rallonges électriques à la prise de votre système UPS De tels branchements peuvent l endommager et entraîner une annulation de sa garantie tout comme celle couvrant le suppresseur de surtension Mises en garde relatives à la batterie Votre système UPS n exige pas d entretien périodique Ne l ouvrez pas quelle que soit la raison sa...

Page 14: ...iche SU1000XL NEMA 5 15 illustrée Modèle SU2200XL illustré Modèle SU1000XL illustré Votre système UPS fonctionnera correctement sans ces connexions Connexion de port série En utilisant le câble série fourni connectez le port série de votre ordinateur à celui de votre système UPS Installez sur votre ordinateur le logiciel de surveillance ASI PowerAlert inclus sur le CD ROM qui convient au système d...

Page 15: ...tème panne de courant ou présente une tension extrêmement élevée Le système UPS alimente alors l équipement à partir de la batterie Voyants du panneau avant Exploitation de base suite Voyants du panneau avant suite VOYANT BYPASS ÉVITEMENT Ce voyant jaune s allume pour signaler que le convertisseur c c c a est désactivé et que le système UPS est en mode d évitement En cours de fonctionnement normal...

Page 16: ...le bloc batterie Tripp Lite approprié à brancher Consultez le guide de l utilisateur fourni avec le bloc batterie externe pour les instructions complètes relatives à son installation et les précautions à prendre Exploitation de base suite Panneau arrière Voyants du panneau avant suite 15 amp 120V NEMA 5 15R 20 amp 120V NEMA 5 20R 20 amp 120V NEMA L5 20R 30 amp 120V NEMA L5 30R Exploitation de base...

Page 17: ...ce élevée Dépannage Dépannage suite Voyants allumés clignotent et problème Solution Allumés FAULT BYPASS LINE DÉFAILLANCE Redémarrez le système UPS Si le ÉVITEMENT ALIMENTATION 25 problème persiste consultez le Problème En mode d évitement en raison service à la clientèle de Tripp Lite d une tension de source basse Allumés FAULT BYPASS LINE DÉFAILLANCE Assurez vous qu il y a suffisamment ÉVITEMENT...

Page 18: ... doivent être prépayés Inscrire le numéro de RMA sur le paquet Si l UPS est encore couvert par la garantie de deux ans joindre une copie de votre facture d achat Renvoyer l UPS pour réparation par un transporteur assuré à l adresse que vous a donnée le technicien de service de Tripp Lite Entreposage Entretien Spécifications La politique de Tripp Lite en est une d amélioration continue Ces spécific...

Reviews: