![Trident TRIDENT 1U1I User Manual Download Page 45](http://html.mh-extra.com/html/trident/trident-1u1i/trident-1u1i_user-manual_1162193045.webp)
GU_TRIDENT_V_1_20_EN
45/47
After having verified the modifications, validate them.
If it is intended to use one of the two standards, go directly to the last page of the program
configuration (start date). Otherwise go to the 3rd configuration page.
Network Characteristics (continued) :
P R O G R A M C O N F I G . 3 / 4
I n t e g r a T i o n 0 1 m n
I s u b s c R i p t 0 0 5 0 0 . 0 A
Here the measurement integration period is entered, as well as the value of the subscript current.
Mean durations :
Integration
This value can be between 1 and 60mn.
TRIDENT can record continuously for 28 days of THD and TDDs measurements with 10 mn
integration periods. For longer periods, the recording duration changes.
Examples :
For 3mn means, TRIDENT can record during a little more than 8 days.
For 30 mns means, TRIDENT can record for nearly 3 months.
The memory of TRIDENT is circular, that is to say that when it is full, the measure program
continues, but the oldest records are replaced by the most recent.
Subscript current : I souscrit
It is the value of the primary of the subscript current. Its value can be between 50A and
99999,9A
After having verified the modifications, validate. You go to the 4th configuration page.
Date of start & end of the program :
P R O G R A M C O N F I G . 4 / 4
D 0 1 / 0 1 / 2 0 0 0 0 0 : 0 0 : 0 0
F 0 1 / 0 1 / 2 0 0 0 0 0 : 0 0 : 0 0
The time and the date of the start (S) and the end (E) of the program must be entered. By default
the start is the current time.
If these times are not modified, the program will start as soon as the last field on this page has
been validated.
If the end time is identical to or before the start time, the program is of unlimited length and will
end only when stopped by the operator.
If the start time is before the current time, the program will start immediately after the last field
has been validated.
If the start time is later than present time, TRIDENT will wait until this time to start the new
program. The device can be disconnected and moved, as this parameter remains memorised.