GU_TRIDENT_V_1_20_EN
24/47
For TRIDENT 3U3I /U :
In the case of voltages in excess of the calibrated voltage (if the voltage of the secondary of a
clamp exceeds 6V on at least one phase), the following warning message appears on the 3rd line.
It disappears as soon as the measured voltage comes down again below 6V.
V A L U E S 1 s e c 1 / 2
V 2 3 1 . 1 2 2 8 . 9 2 3 0 . 4
A l e r t : V m a x = 6 V
P - 1 0 7 7 1 1 8 0 0 9 4 4
The VAL
key moves to the 2nd page :
V A L U E S 1 s e c 2 / 2
U 3 9 7 . 1 3 9 3 . 4 3 9 6 . 7
V e a 0 0 0 . 0 I N e 0 . 0 0
P t o t 1 0 4 5 F 5 0 . 0
The second page shows:
the 3 line voltages U12, U23, U31 in volts,
the voltage between earth and neutral in volts,
the neutral current in Amperes,
the total active power in Watts,
the frequency on the phase V1 in Hertz (averages over 10 seconds).
The VAL key sends back to the welcome screen.
5.2.5
Starting, Stopping and Ending a measurement program.
When the current time reaches or passes the program start time, TRIDENT begins the program.
The red lamp blinks throughout the entire program. The welcome screen appears as follow:
T R I D E N T 3 U 3 I / I V 1 . 7
P R O G R A M R U N N I N G
M A D E S A
If the “marche/arrêt” switch is changed, TRIDENT re-starts the program when power is restored.
In the same way, should the program be interrupted (battery exhausted, M/A switch,...), it will
restart at the re-supply.
To stop the program voluntarily, enter the main menu by pressing the VAL
key.
M A I N M E N U
D i r e c t M e a s u r e m e n t s
- - > P r o g r a m S t o p
C o n s u l t a t i o n