GU_TRIDENT_V_1_20_EN
16/47
Upon delivery, TRIDENT 3U3I contains the following two Standards:
1)
Measurement of simple voltages at Low Voltage
.
Standard
Name
: bt_simple
Voltage Clamps TP
: 1V / 1V.
Current clamps TC
For TRIDENT 3U3I /I : 500 A / 5 A.
For TRIDENT 3U3I/U : 100 A/ 1V.
Type of voltage measurement
: simple.
Nominale primairy voltage
: 230V.
Integration time for slow variations
: 10 mn.
Thresholds
for slow variations.
Swells
: +6 % (243,8 V)
Dips
: -10% (207V)
Voltage faults
:
High threshold :
+6% (243,8V)
Low threshold :
-6% (216,2 V)
Interruption threshold :
-80 % (46V)
Length of long interruption
: 180s. (3 minutes)
Minimum fault variation
: 10ms
Threshold neutral/earth
: 5 V
Frequency threshold
:
High
: 50,5 Hz
Low
: 49,5 Hz
2)
Mesurement of line voltages at Medium Voltage.
Standard name
: HTA_compos
Voltage clamps TP
: 20 000V / 100V.
Current clamps TC
:
For TRIDENT 3U3I /I : 1000 A / 5 A.
For TRIDENT 3U3I/U : 100 A/ 1V.
Type of voltage measurement
: composit.
Nominale primaire voltage
: 20 000V.
Integration time for slow variations
: 10 mn.
Thresholds
for slow variations.
Swells
: +10 % (22 000 V)
Dips
: -10% (18 000V)
Voltage faults
:
High threshold :
+ 4 % (20 800V)
Low threshold :
- 6 % (18 800 V)
Interruption threshold :
- 80 % (4 000V)
Length of long interruption
: 180s. (3 minutes)
Minimum fault variation
: 10ms
Threshold neutral/earth
: 5 V
Frequency threshold
:
High
: 50,5 Hz
Low
: 49,5 Hz
Choose one of the two Standards or the manual configuration, and then validate to advance to
the 2nd configuration page.