Each jumper set has 3 pins, one of which is labeled “N”. The “N” jumper is for set-
ting the switch inputs for dry contact. The “up to 24” pin of the jumper pin is not
labeled. Figure 10 shows how to place jumpers properly.
The jumper must be set before wiring.
If one switch input is dry, the entire section
of eight switch inputs must also be dry contacts, and the associated jumper must
be in the “dry” position. If one switch input is externally powered up to 24 VDC, the
entire section of eight switch inputs must also be up to 24 VDC, and the associated
jumper must be in the “up to 24” position.
1. Remove power to the controller.
Refer to Figure 4. Remove the yellow/blue
power harness by lifting on its terminator block.
2. Set jumpers.
See explanations and Figures 9-10 and Table 1 above.
3. Connect the switches to the controller.
Connect one end of the switch or
contact to terminal “G” and the other to terminal “1-24”. Momentary switches which
have both an ON and Off contact will require two switch inputs on the controller.
See Figure 11 for sample wiring diagrams for each input type. Switch input terminal
blocks are screw type. Land wires by unscrewing, inserting the stripped wire, and
tightening the screw.
3. Reconnect power to the controller.
CAUTION: Before handling any components on the circuit board, the
installer should be grounded to prevent damaging the board.
G
1
2
1
G
1
G
1
G
C
E
1
G
Momentary On Pushbutton
Each contact closure* activates assigned zone. In toggle mode
each contact closure changes state of assigned zone.
Momentary On Pushbutton
Each contact closure* activates assigned zone.
Momentary OFF Pushbutton
Each contact closure* de-activates assigned zone.
Normally Open Maintained Contact
Assigned zone is activated during contact closure*.
Normally Closed Maintained Contact
Assigned zone is activated during contact open*.
Collector
(NPN Darlington Output)
Emitter
(“-” on power source)
*Switch defi ned as normally open polarity in software.
Figure 11
Figure 10
Dry
Position
Up to 24V
Position
LMB Switch Input
Jumper Settings