L35 Series Install Guide
Page 9 of 20
TRIATEK® Lighting • 1025 Cobb Place Blvd. Suite 100 Kennesaw, GA 30144 • 800-241-9173 • www.triateklighting.com
11/30/2004
Due to continuous product improvement, TRIATEK Lighting reserves the right to change product specifi cations without notice.
Neutral
Hot
To
Lights
L35 Series
Latching
Contactors
Circuit
Breakers
From
Lights
From
Lights
From
Lights
From
Lights
To
Lights
To
Lights
To
Lights
Figure 8
L35 Series
Lighting Control Panel
Circuit Breaker Panel
Connecting Switch Inputs
The L35 Series Controller comes standard with 24 programmable switch input ca-
pacity. The 24 termination points are divided into three sections of eight, with each
section containing one ground point ( all three grounds are common ). All points are
numbered, and ground points are labeled “G”.
Do not apply AC voltage to any of
the terminals.
Switch inputs location and labeling on the L35 Series Controller are
shown below.
The inputs can be momentary on, momentary off, momentary on/off, maintained,
linked, or state change. Each section has an accompanying jumper that sets
whether its associated eight inputs will be up to 24 VDC or dry (0 VDC). Table 1 lists
the switch inputs and associated jumpers.
Switch inputs 17-24
Switch inputs 9-16
Switch inputs 1-8
J5
J7
J6
Figure 9
Switch Input Section
Associated Jumper
1- 8
J6
9-16
J7
17-24
J5
Table 1