Connecting the RS-485 Network
The L35 Series is capable of being networked to a Building Automation System or
TRIATEK Lighting’s BASnet LightView over a two or three wire RS-485 communica-
tion network. A terminal block is provided to connect the two communication wires
plus the shield wire. (RS-485 wires are not provided by TRIATEK Lighting.) Use 18
AWG stranded 600V insulated wire. The RS-485 connection location and labeling is
illustrated in Figure 16.
1. Disconnect power to the L35 Series LMB.
Refer to Figure 4.
2. Connect incoming and outgoing transmit “+” to “+” on the RS-485 connec-
tor.
As with switch inputs, a screw type terminal block is provided.
3. Connect incoming and outgoing transmit “-” to “-” on the RS-485 connec-
tor.
4. When a shield wire is used, either splice incoming and outgoing shield
wires together or connect to “S” on the RS-485 connector.
5. Reconnect power to the L35 Series LMB.
Adding and Removing LTR Relays
The L35 Series contains TRIATEK Lighting LTR relays which provide the benefi t
of simple removal and installation. Relay components are shown in Figure 17. For
more information on the LTR relay refer to the L35 Data Sheet obtainable from our
website.
Figure 16
Coil pins
Terminal block
Figure 17
RS-485 Input Detail