L35 Series Install Guide
Page 16 of 20
TRIATEK® Lighting • 1025 Cobb Place Blvd. Suite 100 Kennesaw, GA 30144 • 800-241-9173 • www.triateklighting.com
11/30/2004
Due to continuous product improvement, TRIATEK Lighting reserves the right to change product specifi cations without notice.
Lighting recommends installing the ribbon cables by running them underneath the
electronic boards between the plate and the board. This keeps ribbon cables out
of the way when installing switch wires. Figure 23 shows ribbon cable connection
locations at the LEXP modules and at the LMB. Take care not to drive the mounting
plate screws through the ribbon cable.
When running the ribbon cable to the LMB, run the cable down behind the hinged
plate the LMB is mounted to. Then run the cable over the front of the plate and un-
der the LMB. Bring it out from in between the LMB and its plate and connect it into
its socket labeled, “EXPANSION INPUTS”.
The LEXP board does not need a separate power source. It receives power through
the ribbon cable.
4. Reconnect power to the controller.
Ribbon Cable connection to
the LEXP 1 which receives
inputs 25-56.
Ribbon Cable connection to
the LEXP 2 which receives
inputs 57-88.
Ribbon cable end plugged
into “EXPANSION INPUTS”
socket.
Figure 23
Ribbon cable run behind
hinged backplate and
underneath the LMB