![TriangleTube Prestige Slol 250 Installation And Maintenance Manual Download Page 44](http://html1.mh-extra.com/html/triangletube/prestige-slol-250/prestige-slol-250_installation-and-maintenance-manual_1160001044.webp)
38
Start-Up Preparation
Use of Antifreeze in the Boiler System
NEVER use automotive or ethylene gly-
col antifreeze or undiluted antifreeze in
the primary system as freeze protection.
This can cause severe personal injury,
death or substantial property damage if
ignored.
Determine the antifreeze fluid quantity using
the system water content volume and following
the antifreeze manufacturer instructions.
The water volume of the PRESTIGE Solo is
approximately 3 gallons [12 L] for PRESTIGE
Solo 60 or 5 gallons [19 L] for PRESTIGE Solo
175/250 or 7 gallons [26 L] for PRESTIGE Solo
399 . Remember to include the volume of the
expansion tank.
Check with local codes requirements for the
installation of backflow preventers or actual
disconnection from the boiler’s cold water fill
or make up water supply line.
Massachusetts Code requires the installa-
tion of a backflow preventer if antifreeze
is used.
Ensure the concentration of antifreeze to water
does not exceed a 50/50 ratio.
System water, including additives, must
be practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
Filling the Boiler System
1. Close the boiler drain valve located on the
bottom of the unit and any manual or auto-
matic air vent in the system.
2. Open all system isolation valves.
3. Fill the boiler system to correct system
pressure. Correct pressure will vary with
each application.
Typical residential system fill pressure is
12 psi. System pressure will increase
when system temperature increases.
Operating pressure of the system should
never exceed 25 psi.
4. Purge air and sediment in each zone of the
boiler system through the purge valve.
Open air vents to allow air to be purged in
the zones.
5. Once the system is completely filled and
purged of all air and sediment, check the
system pressure and check/repair any
leaks.
Unrepaired system leaks will cause con-
tinual makeup water to be added to the
boiler. Continual makeup water could
cause mineral buildup within the heat
exchanger, reducing the heat transfer,
causing possible heat buildup and even-
tual heat exchanger failure.
Check Low Water Cut-Off Device
-
The PRESTIGE Solo is provided with a
factory installed LWCO device that mea-
sures system pressure of more than 10 psi.
-
Remove the front jacket panel and check for
continuity across the low water cut-off
device wire terminals. The contacts should
be closed when system pressure is greater
than 10 psi. See item 6, on Fig. 27 page 66
(PRESTIGE Solo 60) or on Fig. 27A page
67 (PRESTIGE Solo 175/250) or Fig. 27B
page 68 (PRESTIGE Solo 399) for location
of the LWCO.
WARNING
NOTICE
NOTICE
NOTICE
WARNING
Summary of Contents for Prestige Slol 250
Page 61: ...55 Factory Setting Parameters FACTORY SETTING FOR PARAMETERS ...
Page 72: ...65 Replacement Parts 5 9 8 1 3 5 2 6 7 Fig 26 PRESTIGE Solo Jacket Components ...
Page 73: ...66 Replacement Parts 8 5 9 2 3 4 4 6 7 1 Fig 27 PRESTIGE Solo 60 Internal Components ...
Page 74: ...67 Replacement Parts 8 5 4 4 10 9 7 1 3 2 6 Fig 27A PRESTIGE Solo 175 250 Internal Components ...
Page 75: ...68 Replacement Parts 8 7 10 1 2 3 4 4 5 6 9 Fig 27B PRESTIGE Solo 399 Internal Components ...
Page 77: ...70 Replacement Parts 7 6 9 1 2 10 12 13 4 3 5 8 Fig 28A PRESTIGE Solo 399 Burner Components ...
Page 78: ...71 3 Fig 29 PRESTIGE Solo Electronic Components Replacement Parts ...
Page 80: ...73 Product Specifications Front View PRESTIGE Solo 175 250 ...
Page 83: ...76 Product Specifications Side View PRESTIGE Solo 175 250 ...