9
Combustion Air and Venting
Outdoor Opening(s) Location. Outdoor open-
ing(s) shall be located in accordance with the
Outdoor Combustion Air section.
Outdoor Opening(s) Size. Outdoor opening(s) shall
be calculated in accordance with the following:
-
The ratio of the interior spaces shall be
the available volume of all communi-
cating spaces divided by the required
volume.
-
The outdoor size reduction factor shall
be 1 minus the ratio of interior spaces.
-
The minimum size of outdoor open-
ing(s) calculated in accordance with the
above outdoor air section multiplied by
the reduction factor.
The minimum
dimension of air openings shall not be
less than 3 in.
Do not install the PRESTIGE Solo into a
common vent with other gas or oil appli-
ances. This may cause flue gas spillage or
appliance malfunction, resulting in possi-
ble severe personal injury, death or sub-
stantial property damage.
Combustion Air and Vent Piping
The PRESTIGE Solo requires a Category IV
venting system, which is designed for pressur-
ized venting and condensate.
The PRESTIGE Solo is certified per ANSI
Z21.13 as a Category IV or Direct Vent (sealed
combustion) appliance. A Category IV appli-
ance utilizes uncontamined indoor or outdoor
air (surrounding the appliance) for combustion.
A Direct Vent appliance utilizes uncontaminat-
ed outdoor air (piped directly to the appliance)
for combustion.
In order to reduce the potential risks
associated with indoor contaminates
(listed on page 5), flammable vapors
and tight housing construction (little or
no infiltration air), it is recommended
to pipe uncontaminated combustion air
directly from the outdoors to the appli-
ance. This practice also promotes higher
system efficiency by reducing heated
indoor air from being exhausted from
the house and replaced by cold infiltra-
tion air into the house.
Install combustion air and vent pipe as
detailed in the PRESTIGE Solo Vent
Supplement included in the boiler
installation envelope. Refer to optional
vent kit instructions for addition vent
installation instructions.
Verify installed combustion air and vent
piping are sealed gas tight and meet all
provided instructions and applicable
codes, failure to comply will result in
severe personal injury of death.
DANGER
NOTICE
BEST PRACTICES
DANGER
Summary of Contents for Prestige Slol 250
Page 61: ...55 Factory Setting Parameters FACTORY SETTING FOR PARAMETERS ...
Page 72: ...65 Replacement Parts 5 9 8 1 3 5 2 6 7 Fig 26 PRESTIGE Solo Jacket Components ...
Page 73: ...66 Replacement Parts 8 5 9 2 3 4 4 6 7 1 Fig 27 PRESTIGE Solo 60 Internal Components ...
Page 74: ...67 Replacement Parts 8 5 4 4 10 9 7 1 3 2 6 Fig 27A PRESTIGE Solo 175 250 Internal Components ...
Page 75: ...68 Replacement Parts 8 7 10 1 2 3 4 4 5 6 9 Fig 27B PRESTIGE Solo 399 Internal Components ...
Page 77: ...70 Replacement Parts 7 6 9 1 2 10 12 13 4 3 5 8 Fig 28A PRESTIGE Solo 399 Burner Components ...
Page 78: ...71 3 Fig 29 PRESTIGE Solo Electronic Components Replacement Parts ...
Page 80: ...73 Product Specifications Front View PRESTIGE Solo 175 250 ...
Page 83: ...76 Product Specifications Side View PRESTIGE Solo 175 250 ...