Pre-Installation Items
-
Reference the appropriate vent supple-
ment for clearance requirements.
To provide serviceability to the unit it is
recommended that the following clear-
ances be maintained:
Top boiler jacket - 24 inches [610 mm].
Front - 24 inches [610 mm].
Bottom boiler piping - 24 inches [610
mm].
Rear - 0 inches
Sides - 6 inches [153 mm]
If the clearances listed above cannot be
maintained or the enclosure in which the
boiler is installed is less than 85 cubic feet,
the space must be ventilated. See page 6
for ventilation requirements.
When maintaining zero clearance or less
than recommended clearances, some
product labeling may become hidden
and unreadable.
When installing the PRESTIGE Solo in
a confined space, sufficient air must be
provided for proper combustion and
venting and to allow, under normal oper-
ating conditions, proper air flow around
the product to maintain ambient temper-
atures within safe limits to comply with
the National Fuel Gas Code NFPA 54 -
latest edition.
Residential Garage Installations
When installing the PRESTIGE Solo in a resi-
dential garage, the following special precautions
per NFPA 54/ANSI Z223.1 must be taken:
-
Mount the unit a minimum 18 inches
[458 mm] above the floor level of the
garage. Ensure the burner and ignition
devices / controls are no less than 18
inches [458 mm] above the floor level.
-
Locate or protect the unit in a manner
so it cannot be damaged by a moving
vehicle.
Boiler Freeze Protection Feature
The boiler control has a freeze protection feature
built in. This feature monitors the boiler temper-
ature and responds as follows when no call for
heat is present:
-
46ºF Boiler circulator is ON
-
38ºF Boiler circulator is ON and burner
operates at low fire
-
50ºF Burner OFF and boiler circulator
operates for approximately 10 minutes
The boiler freeze protection feature is
disabled during a hard lockout, however
the CH circulator will operate.
The boiler freeze protection feature is
designed to protect the boiler. The boiler
should be installed in a primary/sec-
ondary piping arrangement if it is
installed in an unheated space or
exposed to water temperatures of 46ºF or
less. See Section IV for primary/sec-
ondary piping examples. See Section IX
for antifreeze guides.
CAUTION
CAUTION
WARNING
NOTICE
WARNING
BEST PRACTICES
4
Summary of Contents for Prestige Slol 250
Page 61: ...55 Factory Setting Parameters FACTORY SETTING FOR PARAMETERS ...
Page 72: ...65 Replacement Parts 5 9 8 1 3 5 2 6 7 Fig 26 PRESTIGE Solo Jacket Components ...
Page 73: ...66 Replacement Parts 8 5 9 2 3 4 4 6 7 1 Fig 27 PRESTIGE Solo 60 Internal Components ...
Page 74: ...67 Replacement Parts 8 5 4 4 10 9 7 1 3 2 6 Fig 27A PRESTIGE Solo 175 250 Internal Components ...
Page 75: ...68 Replacement Parts 8 7 10 1 2 3 4 4 5 6 9 Fig 27B PRESTIGE Solo 399 Internal Components ...
Page 77: ...70 Replacement Parts 7 6 9 1 2 10 12 13 4 3 5 8 Fig 28A PRESTIGE Solo 399 Burner Components ...
Page 78: ...71 3 Fig 29 PRESTIGE Solo Electronic Components Replacement Parts ...
Page 80: ...73 Product Specifications Front View PRESTIGE Solo 175 250 ...
Page 83: ...76 Product Specifications Side View PRESTIGE Solo 175 250 ...