Installation
(for qualified installers only)
9
© Travis Industries
4150624
100-01425
Fireplace Placement Requirements
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
Fireplace should be located out of traffic and away from furniture and draperies.
Fireplace must be placed so the gaps below and above the glass frame do not become blocked.
Fireplace may be placed in a bedroom. Please be aware of the large amount of heat this appliance produces
when determining a location.
Clearances
(a) Clearance to Side of Fireplace 5/8” (16mm). Do not place insulation in this space.
NOTE: Drywall or other combustible may contact the side of the fireplace in front of the framing. The
material must not protrude in front of the fireplace and may be a maximum ½” (13mm) thick.
(b) When installed, walls in front of the fireplace must be a minimum 3” (77mm) to the side of the fireplace.
b
a
b
Raised Fireplaces
The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace and vent.
The base of the fireplace must be a minimum 64” (1626mm) below the room ceiling.
The firebox opening is approximately 10.375” (264mm) above the base of the fireplace. For a
typical raised fireplace of 36” (915mm), place the fireplace on a platform 25.625” (651mm) tall.