Installation
(for qualified installers only)
27
© Travis Industries
4150624
100-01425
Minimum Vent Configuration
Use 5x8” Diameter Coaxial Vent
NOTE
: Use the included pipe shield and both 8” firestops (use on front and back of wall
penetration).
The termination must fall within the shaded area shown in the chart. Use the indicated
restrictor positions.
One 45° elbow may be used on the horizontal run.
HINT
: Use minimum vent kit “H” from Travis Industries (additional vent will be required).
12" (305mm) Section
3 feet (0.915m)
0 feet
0 feet
Min. 24" (600mm) Horizontal Section
Max. 18' (5.5M) Horizontal Section(s)
Exhaust Restrictor # 1 (stock)
Diffuser Closed (stock)
Intake Restrictor # 1 (stock)
5 feet (1.5 m)
10 feet (3 m)
15 feet (4.5 m)
18' max (5.5 m)
NG (Natural Gas)
12" (305mm) Section
3 feet (0.915m)
0 feet
0 feet
Min. 24" (600mm) Horizontal Section
Max. 14' (4.2M) Horizontal Section(s)
Exhaust Restrictor # 0 (removed)
Diffuser Closed (stock)
Intake Restrictor # 1 (stock)
5 feet (1.5 m)
10 feet (3 m)
14' max (4.2 m)
LP (Propane)