Temperature Sensor Configuration
The Threshold Settings table lists the threshold severity, relation, and comparison value for a sensor listed in the
Entity-MIB Physical Table.
Temperature
: displays the most recent temperature measurement obtained by the agent for this
sensor.
Temperature Status
: displays the operational status of the physical sensor.
o
OK
- indicates that the agent can obtain the sensor value.
o
Unavailable
- indicates that the agent presently cannot obtain the sensor value.
o
Nonoperational
- indicates that the agent believes the sensor is broken. The sensor could have a
hard failure (disconnected wire), or a soft failure (e.g., out-of-range, jittery, or wildly fluctuating
readings).
Relay Enabled
: select True to enable relay operation. The IONPS-D-R1 supports a Dry Contact Relay
which can be enabled or disabled in the Entity Sensor Thresholds for "Temperature", "Voltage",
"Power", and "Fan". See the example below for operating details.
Index
: use the cursor to select an index line / number that uniquely identifies an entry in the Threshold
Table. The index permits the same sensor to have several different threshold values set.
Severity
: select
Minor
,
Major
,
Critical
or
Other
. Critical is the most severe, Major is the next most
severe, and Minor is the least severe. The system might shut down the sensor associated FRU
automatically if the sensor value reaches the Critical problem threshold.