Transition Networks, Inc.
IONPS-D-R1 User Guide
33707 Rev. A
Page
6
of
50
1. Introduction and Description
IONPS-D-R1 Description
Transition Networks’ IONPS-D-R1 power module can deliver power or provide optional, redundant DC power for
the ION219 chassis. The ION platform is an intelligent, high-density, multi-protocol system supporting a variety
of network interface devices. Designed for both carrier class and enterprise network applications where multiple
points of fiber integration and secure network management of the fiber interface devices is essential.
The ION219 chassis can support up to two power supply modules which mount in the rear of the chassis.
A single power supply can be used to power all the devices installed in the chassis; however the system can be
made redundant with the use of a second power supply. In this configuration, the power supplies operate in an
instant-fail-over mode. The IONPS-D-R1 is shown below:
Figure 1: IONPS-D-R1 (DC) Power Supply
General Specifications
The IONPS-D-R1 is designed to meet these standards:
IEEE Standards
IEEE 802.3™-2000
Emission Compliance
EN55022 Class A
Immunity Compliance
EN55024
Safety Compliance
UL Listed (UL60950), FCC Class A, CISPR Class A, CE Mark
Power input
48VDC (40 – 60VDC) @ 5A
(typical for a fully-loaded chassis); 10 Amps max
Under-voltage lockout
40VDC max, 38VDC min
Inrush current
5A max
Power output
12VDC @ 12 Amp max
DC Power Input
40-60 VDC @ 10A max.
Fuse
12A / 450VAC. Caution: For continued protection against risk of fire, replace
with same Type & Rating of fuse. Disconnect power source before servicing.