Troubleshooting and Common Questions

Troubleshooting and Common Questions

Problem

Explanation/Resolution

Widgets on custom 
graphics do not follow the 
setpoint limit range set on 
the Options tab within 
Settings

Even though they look similar to the main screen, these widgets do not 
follow the Setpoint limit range set on the Options tab. The limits for the 
widgets are set within Tracer Graphics Editor widget property dialog.

Communication loss

If communication loss occurs between the System Controller and the 
display, or between System Controller and the unit controllers, some 
elements of the screen may disappear temporarily and/or the display 
may restart. When this occurs, in addition to troubleshooting the 
communication loss, press the power button to restart the display.

Changes to site via the 
System Controller web 
interface

If the System Controller programming changes (such as schedules 
added, zones renamed, or graphics loaded), after the display has been 
started, the display should reflect the changes after a few minutes and 
may restart. If the display does not update in a timely manner, restart the 
display by pressing the power button on the back of the display.

Up or down arrow are 
disabled 

Potential causes: 

• Setpoint is controlled locally at the zone sensor (such as 

thumbwheel).

• The user does not have access to the setpoint.
• The setpoint is controlled at a higher priority.
• The setpoint is out of the range of the limits. The range is applied to 

the relinquish default value of the setpoint. 

Setpoint doesn’t seem to 
be controlling the HVAC

Check in the System Controller web user interface that the unit controller 
is receiving the setpoint. Notes regarding priority level:
• The main screen controls the setpoint of zone (area or space) at 

control priority level 13 as default or at the user's simplified override 
level.

• Custom graphics with a setpoint widget, similar to the main screen, 

can have the override priority set in TGE as a property of the widget. 
If you want the custom graphic to write at the same level as the display 
main screen, keep the default override priority (level 13).

No timer appears for a 
space that is controlled by 
an area before unoccupied 
transition

When approaching an unoccupied time (within two hours), the display 
will show a countdown timer to unoccupied mode on the main screen. 
This works well for spaces and areas that are members of a schedule. No 
timer will appear for a space that is controlled by an area, if the area is 
the member of the schedule.
For example, changeover systems require the VAV boxes (spaces) to be 
members of an area as well as the VAS. Also, the area should be setup 
as a member of a schedule to control occupancy. Therefore, as the 
schedule approaches an unoccupied period, the display main screen will 
not show a countdown timer for any of the VAV boxes, since the VAV 
boxes are controlled by the Area rather than directly as Schedule 
members. The VAV box on the main screen will go from occupied mode 
to unoccupied mode without any countdown timer. No functionality is 
affected. The system will control as programmed.

Summary of Contents for Tracer Concierge

Page 1: ...lled adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and...

Page 2: ...ditioning industry All technicians who handle refrigerants must be certified according to local rules For the USA the Federal Clean Air Act Section 608 sets forth the requirements for handling reclaim...

Page 3: ...ath or serious injury Technicians in order to protect themselves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as...

Page 4: ...ng Additional WCIs to an Existing Network 8 Related Literature 8 Step 12 Tracer UC210 Setup for Changeover Systems 9 Step 13 System Controller Setup 10 Discover and Install Rooftop Units and VAV Boxes...

Page 5: ...ce guide BAS SVX55 See also Step 11 Verify that any rooftop units and VAV boxes with Air Fi Wireless are addressed properly per the submittal and or the Air Fi Wireless Network Best Practice Guide BAS...

Page 6: ...Areas with high humidity High traffic areas to reduce accidental damage or tampering Placing the sensor inside metal enclosures Typical Signal Range The WCI has a typical signal range radius of 200 ft...

Page 7: ...ess network Best Practice Power up all devices in the network at the same time If you are unable to do this power them up in the following order 1 All WCIs 2 All unit controllers UC210 UC400 UC600 BCI...

Page 8: ...ciate with the WCI Adding Additional WCIs to an Existing Network 1 Press the OPEN_NET button on the System Controller WCI to open the network for joining for one hour Every member WCI will indicate th...

Page 9: ...that it reflects the air temperature from the zones and is unaffected by the bypassed airflow With Tracer TU setup Tracer UC210s for use with dampers without flow sensing 1 Change the box type to gen...

Page 10: ...controlled by Tracer Concierge See Technical Support for more details Create a Tracer 10 inch Display User CreateanewSystemControlleruserforTracerConcierge Tracer10 inchDisplaywilluse these credential...

Page 11: ...a to be shown on the display Figure 4 Configure area members Important For every space that is a member of an Area create Global Referencers to send setpoints from area as adjusted on the display to i...

Page 12: ...ed heating and cooling When an area has only lighting members the Tracer Display main screen shows a light bulb and override button No up down arrows are shown See the Parking Lot Lights example in Fi...

Page 13: ...r Constant Volume Air System 3 Enable the optional Optimization functions and click Next Figure 10 Create VAS Note Duct Static Optimization is not supported for Constant Volume systems 4 Select the Ai...

Page 14: ...on the DAT High and Low Limit definition Using Reliatel controls as an example when there is no DAT sensor the BCI R will set the value for DAT to 65 535 and put the point out ofservice When the point...

Page 15: ...e main screen System Controller graphic navigation buttons are not supported in Tracer Concierge Instead use target or link Best practices for custom graphics Limit or do not use navigation between cu...

Page 16: ...ller The Display mounts to the wall using a VESA mount The required VESA mounting bracketsizeis75mmx75mm AVESAmount OrderNumberX05010511010 isavailable as an accessory from Trane but any standard VESA...

Page 17: ...lternatively for a Wi Fi connection connect the Ethernet cable from System Controller Port 2 to the Wi Fi router Port 1 2 Plug in the display power adapter to an appropriate wall outlet 3 If the displ...

Page 18: ...System Controller via the wireless network a Choose Wi Fi and wait for the display to refresh available Wi Fi networks b Ifusing theWi Firouterfrom Trane selectciscosb1 andverifysecurityis WPA2 PSK c...

Page 19: ...ress field Tracer Concierge will attempt a secure connection via https first If not available it will establish a standard connection http 9 Select the Zones tab Figure 17 Zones tab 10 Set the zone or...

Page 20: ...e Options tab you can change the setpoint limit from 1 9 or disable it entirely Note This setpoint limit applies to the setpoints on the main screen and will not apply to any custom graphics 15 Select...

Page 21: ...a 15 minute timer This is a higher priority than the schedule level 15 but not as hight as the display level 13 The override should take affect over the schedule but the display will be able to contr...

Page 22: ...the limits The range is applied to the relinquish default value of the setpoint Setpoint doesn t seem to be controlling the HVAC Check in the System Controller web userinterface thatthe unit controlle...

Page 23: ...rong address For factory addressed WCIs verify address is correct Verify each WCI address after installation If sensor is installed check for error code at sensor Initiate network formation and resolv...

Page 24: ...ed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial and residen...

Reviews: