Installation Order

Installation Order

• Hardware setup (Steps 1-8). See Tracer Concierge System Part 1 of 2: Hardware Setup 

(BAS-SVN135*-EN).

• Setup System Controller and display (Steps 9-17, this document). 

Step 9: Verify Package Contents

Note: 

Tracer Concierge 2.0 requires System Controller 4.0 as of December 2016.

Step 10: Installation Checklist

Verify that hardware installation is complete:

Verify the System Controller panel is attached to the wall and power is wired to it.

Verify XM Module I/O terminations are wired appropriately per the submittal. 

Verify System Controller Air-Fi

®

 Wireless is addressed properly and/or the Air-Fi 

Wireless Network Best Practice guide BAS-SVX55. See also Step 11. 

Verify that any rooftop units and VAV boxes with Air-Fi Wireless are addressed 

properly per the submittal and/or the Air-Fi Wireless Network Best Practice Guide 
BAS-SVX55.

Verify the Ethernet Cable for the customer’s network is connected to System Controller 
Ethernet Port 1 (if applicable).

Follow this best practice for ReliaTel BCI for Constant Volume Rooftops: install a duct 

temperature probe (part number 4190-7020) in the return air duct and wire the sensor 
to the BCI-R's space temperature input. Unless the HVAC system is a Changeover 
System, in which case place the duct temperature probe in the return air duct, before/
upstream of the bypass damper. 

Table 1.

Packaged contents

Item

Quantity

10.1 in. Display

1

Display power cord

1

Installation Instructions

1

User Guide

1

USB-to-Ethernet Adapter

1

VESA Mounting Bracket

1

Ethernet Cable 

1

Summary of Contents for Tracer Concierge

Page 1: ...lled adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and...

Page 2: ...ditioning industry All technicians who handle refrigerants must be certified according to local rules For the USA the Federal Clean Air Act Section 608 sets forth the requirements for handling reclaim...

Page 3: ...ath or serious injury Technicians in order to protect themselves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as...

Page 4: ...ng Additional WCIs to an Existing Network 8 Related Literature 8 Step 12 Tracer UC210 Setup for Changeover Systems 9 Step 13 System Controller Setup 10 Discover and Install Rooftop Units and VAV Boxes...

Page 5: ...ce guide BAS SVX55 See also Step 11 Verify that any rooftop units and VAV boxes with Air Fi Wireless are addressed properly per the submittal and or the Air Fi Wireless Network Best Practice Guide BAS...

Page 6: ...Areas with high humidity High traffic areas to reduce accidental damage or tampering Placing the sensor inside metal enclosures Typical Signal Range The WCI has a typical signal range radius of 200 ft...

Page 7: ...ess network Best Practice Power up all devices in the network at the same time If you are unable to do this power them up in the following order 1 All WCIs 2 All unit controllers UC210 UC400 UC600 BCI...

Page 8: ...ciate with the WCI Adding Additional WCIs to an Existing Network 1 Press the OPEN_NET button on the System Controller WCI to open the network for joining for one hour Every member WCI will indicate th...

Page 9: ...that it reflects the air temperature from the zones and is unaffected by the bypassed airflow With Tracer TU setup Tracer UC210s for use with dampers without flow sensing 1 Change the box type to gen...

Page 10: ...controlled by Tracer Concierge See Technical Support for more details Create a Tracer 10 inch Display User CreateanewSystemControlleruserforTracerConcierge Tracer10 inchDisplaywilluse these credential...

Page 11: ...a to be shown on the display Figure 4 Configure area members Important For every space that is a member of an Area create Global Referencers to send setpoints from area as adjusted on the display to i...

Page 12: ...ed heating and cooling When an area has only lighting members the Tracer Display main screen shows a light bulb and override button No up down arrows are shown See the Parking Lot Lights example in Fi...

Page 13: ...r Constant Volume Air System 3 Enable the optional Optimization functions and click Next Figure 10 Create VAS Note Duct Static Optimization is not supported for Constant Volume systems 4 Select the Ai...

Page 14: ...on the DAT High and Low Limit definition Using Reliatel controls as an example when there is no DAT sensor the BCI R will set the value for DAT to 65 535 and put the point out ofservice When the point...

Page 15: ...e main screen System Controller graphic navigation buttons are not supported in Tracer Concierge Instead use target or link Best practices for custom graphics Limit or do not use navigation between cu...

Page 16: ...ller The Display mounts to the wall using a VESA mount The required VESA mounting bracketsizeis75mmx75mm AVESAmount OrderNumberX05010511010 isavailable as an accessory from Trane but any standard VESA...

Page 17: ...lternatively for a Wi Fi connection connect the Ethernet cable from System Controller Port 2 to the Wi Fi router Port 1 2 Plug in the display power adapter to an appropriate wall outlet 3 If the displ...

Page 18: ...System Controller via the wireless network a Choose Wi Fi and wait for the display to refresh available Wi Fi networks b Ifusing theWi Firouterfrom Trane selectciscosb1 andverifysecurityis WPA2 PSK c...

Page 19: ...ress field Tracer Concierge will attempt a secure connection via https first If not available it will establish a standard connection http 9 Select the Zones tab Figure 17 Zones tab 10 Set the zone or...

Page 20: ...e Options tab you can change the setpoint limit from 1 9 or disable it entirely Note This setpoint limit applies to the setpoints on the main screen and will not apply to any custom graphics 15 Select...

Page 21: ...a 15 minute timer This is a higher priority than the schedule level 15 but not as hight as the display level 13 The override should take affect over the schedule but the display will be able to contr...

Page 22: ...the limits The range is applied to the relinquish default value of the setpoint Setpoint doesn t seem to be controlling the HVAC Check in the System Controller web userinterface thatthe unit controlle...

Page 23: ...rong address For factory addressed WCIs verify address is correct Verify each WCI address after installation If sensor is installed check for error code at sensor Initiate network formation and resolv...

Page 24: ...ed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial and residen...

Reviews: