RLC-SVU01B-E4
57
Diagnostics
5BD
5B0
5B1
5B2
5B3
5AC
5AD
5AE
5AF
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
Latch
Same as Suction Refrigerant
Pressure Transducer - Circuit 1,
Compressor 1A
Immediate
Remote
Suction Refrigerant
Pressure Transducer -
Circuit 1,
Compressor 2b
Latch
The Transition Complete input
was found to be opened with
the compressor motor running
after a successful completion of
transition. This is active only for
Y-Delta, Auto-Transformer,
Primary Reactor, and X-Line
Starters. To prevent this
diagnostic from occurring as
the result of a power loss to the
contactors, the minimum time
to trip must be greater than the
trip time for the power loss
diagnostic.
Immediate
Local
Transition Complete
Input Opened -
Compressor 1A
Latch
Same as Transition Complete
Input Opened - Compressor 1A
Immediate
Local
Transition Complete
Input Opened -
Compressor 1B
Latch
Same as Transition Complete
Input Opened - Compressor 1A
Immediate
Local
Transition Complete
Input Opened -
Compressor 2A
Latch
Same as Transition Complete
Input Opened - Compressor 1A
Immediate
Local
Transition Complete
Input Opened -
Compressor 2B
Latch
The Transition Complete input
was found to be shorted before
the compressor was started.
This is active for all
electromechanical starters.
Immediate
Local
Transition Complete
Input Shorted -
Compressor 1A
Latch
Same as Transition Complete
Input Opened - Compressor 2B
Immediate
Local
Transition Complete
Input Shorted -
Compressor 1B
Latch
Same as Transition Complete
Input Opened - Compressor 2B
Immediate
Local
Transition Complete
Input Shorted -
Compressor 2A
Latch
Same as Transition Complete
Input Opened - Compressor 2B
Immediate
Local
Transition Complete
Input Shorted -
Compressor 2B