RLC-SVU01B-E4
32
Diagnostics
Latch
Continual loss of
communication between the
MP and the Functional ID has
occurred for a 30 second
period. MP will nonvolatilely
hold the lockout state (enabled
or disabled) that was in effect
at the time of comm loss.
Comm Loss: External
Circuit Lockout,
Circuit #1
Special
Mode
Remote
NonLatch
Continual loss of
communication between the
MP and the Functional ID has
occurred for a 30 second
period. Chiller shall discontinue
use of the External Current
limit setpoint and revert to the
next higher priority for Current
Limit setpoint arbitration.
Comm Loss: External
Current Limit
Setpoint
Special
Mode
Remote
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Comm Loss: Fan
Control Circuit #1,
Stage #1
Normal
Remote
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Comm Loss: Fan
Control Circuit #1,
Stage #3
Normal
Remote
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Latch
Same as Comm Loss: Chilled
Water Flow Switch
Normal
Remote
Comm Loss: Fan
Control Circuit #1,
Stage #2
Comm Loss: Fan
Control Circuit #1,
Stage #4
Comm Loss: Fan
Control Circuit #2,
Stage #1
Comm Loss: Fan
Control Circuit #2,
Stage #2
Comm Loss: Fan
Control Circuit #2,
Stage #3
Latch
Same as Comm Loss: External
Circuit Lockout, Circuit #1
Comm Loss: External
Circuit Lockout,
Circuit #2
Special
Mode
Remote