Diagnostics
1F1
1F2
1F3
1F4
5C7
5C8
5C5
5C6
5C9
5CA
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
Latch
As part of the normal start
sequence to apply power to the
compressor, the Shorting
Contactor (1K3) and then the
Main Contactor (1K1) were
energized. 1.6 seconds later
there were no currents
detected by the CT's for the last
1.2 Seconds on all 3 phases.
The test above applies to all
forms of starters except
Adaptive Frequency Drives.
Immediate
Local
Latch
Same as Starter Fault Type III -
Compressor 1A
Immediate
Local
Starter Fault Type III -
Compressor 1B
Latch
Same as Starter Fault Type III -
Compressor 1A
Immediate
Local
Starter Fault Type III -
Compressor 2A
Latch
Same as Starter Fault Type III -
Compressor 1A
Immediate
Local
Starter Fault Type III -
Compressor 2B
Starter Fault Type III -
Compressor 1A
Latch
Checksum on RAM copy of the
Starter LLID configuration
failed
Info
Local
Starter Module
Memory Error Type 1 -
Starter 2A
Latch
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Info
Local
Starter Module
Memory Error Type 1 -
Starter 2B
Latch
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Info
Local
Starter Module
Memory Error Type 1 -
Starter 1A
Latch
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Info
Local
Starter Module
Memory Error Type 1 -
Starter 1B
Latch
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Immediate
Local
Starter Module
Memory Error Type 2 -
Starter 1A
Latch
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Immediate
Local
Starter Module
Memory Error Type 2 -
Starter 1B