RLC-SVU01B-E4
39
AB
27D
3F9
6B9
6BA
ED
Diagnostics
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
Latch
Bad Sensor or LLID
Normal
Remote
Evaporator Leaving
Water Temperature
Sensor
Latch
Bad Sensor or LLID
Immediate
Remote
Evaporator Liquid
Level Sensor -
Circuit 1
Latch
Bad Sensor or LLID
Immediate
Remote
Evaporator Liquid
Level Sensor -
Circuit 2
Latch
This diagnostic is effective only
with Remote Evaporator units.
The liquid level of the
respective evaporator was not
seen to be below the level of-
21.2 mm (0.83 in) within 5
minutes of the commanded
opening of its Drain Valve
Solenoid. The diagnostic will
not be active if the drain valve
is commanded closed.
NA
Remote
Evaporator Rfgt Drain
- Circuit 1
Latch
Same as Evaporator Rfgt Drain
- Circuit 1
NA
Remote
Evaporator Rfgt Drain
- Circuit 2
NonLatch
a. The chilled water flow switch
input was open for more than
6-10 contiguous seconds.
b. This diagnostic does not de-
energize the evaporator pump
output
c. 6-10 seconds of contiguous
flow shall clear this diagnostic.
d. Even though the pump times
out in the STOP modes, this
diagnostic shall not be called
out in the STOP modes. Note
that this diagnostic will not
light the red diagnostic light on
the EasyView display.
Immediate
Remote
Evaporator Water
Flow Lost