RLC-SVU01B-E4
49
Diagnostics
D7
19C
19D
19E
19F
184
Reset
Level
Hex
Code
Persistence
Severity
Diagnostic Name and
Source
Criteria
NonLatch
a. Line voltage above + 10% of
nominal. [Must hold = + 10 %
of nominal. Must trip = + 15 %
of nominal. Reset differential =
min. of2% and max. of 4%.
Time to trip = minimum of 1
min. and maximum of 5 min.)
Design: Nom. trip: 60 seconds
at greater than 112.5%, + or-
2.5%, Auto Reset at 109% or
less.
Immediate
Remote
Over Voltage
Latch
a) No current was sensed on
one or two of the current
transformer inputs while
running or starting (See
Nonlatching Power Loss
Diagnostic for all 3 phases lost
while running). Must hold =
20% RLA. Must trip = 5% RLA.
Time to trip shall be longer
than guaranteed reset on
Starter Module at a minimum,
3 seconds maximum. Actual
design trippoint is 10%. The
actual design trip time is 2.64
seconds. b) If Phase reversal
protection is enabled and
current is not sensed on one or
more current transformer
inputs. Logic will detect and
trip in a maximum of 0.3
second from compressor start.
Immediate
Local
Phase Loss -
Compressor 1A
Latch
Same as Phase Loss -
Compressor 1A
Immediate
Local
Phase Loss -
Compressor 1B
Latch
Same as Phase Loss -
Compressor 1A
Immediate
Local
Phase Loss -
Compressor 2A
Latch
Same as Phase Loss -
Compressor 1A
Immediate
Local
Phase Loss -
Compressor 2B
Latch
A phase reversal was detected
on the incoming current. On a
compressor startup the phase
reversal logic must detect and
trip in a maximum of .3 second
from compressor start.
Immediate
Local
Phase Reversal -
Compressor 1A