61
Relay outputs
Relay Number:
1
2
Parameter:
323
326
Value:
No function (NO FUNCTION)
[0]
[0]
Drive ready (READY)
[1]
[1]
Waiting for start (ENABLED & NO WARNING)
[2]
[2]
Running (RUNNING)
[3]
★
[3]
Running at reference value (RUNNING AT REFERENCE)
[4]
[4]
Running, no warning (RUNNING NO WARNING)
[5]
[5]
Local reference active (DRIVE IN LOCAL REF)
[6]
[6]
Remote controlled references active (DRIVE IN REMOTE REF.)
[7]
[7]
Alarm (ALARM)
[8]
[8]
Alarm or warning (ALARM OR WARNING)
[9]
[9]
No alarm (NO ALARM)
★
[10]
[10]
Current limit (CURRENT LIMIT)
[11]
[11]
Safety interlock (SAFETY INTERLOCK)
[12]
[12]
Start command active (START SIGNAL APPLIED)
[13]
[13]
Running in reverse (RUNNING IN REVERSE)
[14]
[14]
Thermal warning (THERMAL WARNING)
[15]
[15]
Hand mode active (DRIVE IN HAND MODE)
[16]
[16]
Auto mode active (DRIVE IN AUTO MODE)
[17]
[17]
Sleep mode active (SLEEP MODE)
[18]
[18]
Output frequency lower than low frequency, parameter 223 (F OUT < F LOW)
[19]
[19]
Output frequency higher than high frequency, parameter 224 (F OUT > F HIGH)
[20]
[20]
Out of frequency range (FREQ RANGE WARN.)
[21]
[21]
Output current lower than low current, parameter 221 (I OUT < I LOW)
[22]
[22]
Output current higher than high current, parameter 222 (I OUT > I HIGH)
[23]
[23]
Out of current range (CURRENT RANGE WARN.)
[24]
[24]
Out of feedback range (FEEDBACK RANGE WARN.)
[25]
[25]
Out of reference range (REFERENCE RANGE WARN.)
[26]
[26]
Relay 123 (RELAY 123)
[27]
[27]
Input phase loss (MAINS PHASE LOSS)
[28]
[28]
Control word bit 11/12 (CONTROL WORD 11/12)
[29]
[29]
Relay Outputs
Relay 1:
Relay 2:
4 - 5 normally open
Maximum:
30 VAC, 1 A,
42.5 VDC, 1 A
The low voltage relay terminals are
located on the control wiring terminal
strips.
Function:
Relay outputs 1 and 2 can be used to give the present status or a
warning. See the description of options in Analog/Digital Outputs.
Control word bit 11/12
[29]. Relay 1 and relay 2 can be activated
through serial communication. Bit 11 activates relay 1 and bit 12
activates relay 2.
1 - 3 normally closed, 1 - 2 normally open
Maximum:
240 VAC/DC, 2 A
Minimum:
24 VAC, 100 mA;
24 VDC, 10 mA
The high voltage relay connections are located
near the input power and motor terminals.
If parameter 556,
Bus Time Interval Function,
becomes active, relay 1
and relay 2 will cut out if they are activated through serial
communication.
Description of choice:
Select the output relay function.
Relay 02
✭
I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.