103
0..
Operation and Display
#
Parameter
Factory Setting
Range
Changes
4-Setup
Conversion
Data
Description
During Operation
Index
Type
001
Language
ENGLISH
Yes
No
0
5
002
Active Setup
SETUP 1
Yes
No
0
5
003
Copying of Setups
NO COPY
No
No
0
5
004
LCP Copy
NO COPY
No
No
0
5
005
Max Value of User-defined Readout
100.000
0 - 999.999,999
Yes
Yes
-2
4
006
Unit for User-defined Readout
%
Yes
Yes
0
5
007
Big Display Readout
FREQUENCY, %
Yes
Yes
0
5
008
Small Display Readout 1.1
REFERENCE, %
Yes
Yes
0
5
009
Small Display Readout 1.2
MOTOR CURRENT, A
Yes
Yes
0
5
010
Small Display Readout 1.3
POWER, HP
Yes
Yes
0
5
011
Unit of Local Reference
% OF F MAX
Yes
Yes
0
5
012
Hand Start on LCP
ENABLE
Yes
Yes
0
5
013
OFF/STOP on LCP
ENABLE
Yes
Yes
0
5
014
Auto Start on LCP
ENABLE
Yes
Yes
0
5
015
Reset on LCP
ENABLE
Yes
Yes
0
5
016
Lock for Data Change
NOT LOCKED
Yes
Yes
0
5
017
Operating State at Power-up
AUTO RESTART
Yes
Yes
0
5
Factory Settings (continued)
Changes During Operation:
Yes means that the parameter can be changed while the drive is in
operation. No means that the drive must be stopped before a change
can be made.
4-Setup:
Yes means that the parameter can be programmed individually in
each of the four setups. The same parameter can have four different
data values. No means that the data value will be the same in all four
setups.
Conversion Index:
This number refers to a conversion figure to be used when writing or
reading to or from the drive by means of serial communication.
Since a parameter value can only be transferred as a whole number, a
conversion factor must be used to transfer decimals.
Example:
Parameter 201:
Minimum Frequency
, conversion factor 0.1. If
parameter 201 is to be set to 10 Hz, a value of 100 must be
transferred, since a conversion factor of 0.1 means that the transferred
value will be multiplied by 0.1. A value of 100 will, therefore, be
understood as 10.0.
Data type:
Data type shows the type and length of the packet.
Conversion Index
Conversion Factor
74
3.6
2
100.0
1
10.0
0
1.0
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
Conversion Index Factors
Data Type Descriptions