![background image](http://html1.mh-extra.com/html/trane/tr1-6002/tr1-6002_installation-and-operation-manual_1149812014.webp)
14
Current ratings are in amps. Torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
200 to 208 VAC Auxiliary Control Panel Tightening Torques
200 to 240 VAC Terminal Tightening Torque
380 to 460 VAC Terminal Tightening Torque
Max . Drive
Output Current
Torque
in-lbs (Nm )
6.9
5 (0.6)
7.8
5 (0.6)
11
5 (0.6)
17.5
5 (0.6)
26
17 (1.8)
33
17 (1.8)
48.3
28 (3.0)
62.1
28 (3.0)
78.2
28 (3.0)
92
35 (4.0)
115
100 (11.3)
143
100 (11.3)
170
100 (11.3)
Max. Drive
Output Current
Torque
in-lbs (Nm)
Max. Drive
Output Current
Torque
in-lbs (Nm)
to 10
5 (0.6)
147
100 (11.3)
16
5 (0.6)
177
100 (11.3)
24
17 (1.8)
212
100 (11.3)
32
17 (1.8)
260
100 (11.3)
37.5
17 (1.8)
315
100 (11.3)
44
28 (3.0)
368
100 (11.3)
61
28 (3.0)
487
372 (42.0)
73
28 (3.0)
594
372 (42.0)
90
28 (3.0)
649
372 (42.0)
106
100 (11.3)
746
372 (42.0)
Terminal Tightening Torque
Tighten terminals connecting the drive input power, output to the
motor(s) and ground to the values shown in the tables below. Drives
with 200 to 240 volts of 88 amps and less, and drives with 380 to 600
volts of 90 amps and less, have removable terminal blocks with
screws. Larger drives have fixed bolts. (See the drive nameplate for
maximum drive output current.)
All current ratings are in amps.
200-208 V Hp
Ra ting
Ove rloa d
Re la y
In/Out Pow e r
Te rmina l
CTK Bre a ke r
Ma in Disco
Sw itch
Drive Disco
Sw itch
MN/BYP Fuse
BLK
Drive Fuse
BLK
Ground
Te rm ina l
1
17 (1.9)
15 (1.7)
22 (2.5)
7 (.8)
7 (.8)
25 (2.8)
35 (4.0)
45 (5.1)
1 1/2
17 (1.9)
15 (1.7)
22 (2.5)
7 (.8)
7 (.8)
25 (2.8)
35 (4.0)
45 (5.1)
2
17 (1.9)
15 (1.7)
22 (2.5)
7 (.8)
7 (.8)
25 (2.8)
35 (4.0)
45 (5.1)
3
17 (1.9)
15 (1.7)
22 (2.5)
7 (.8)
7 (.8)
25 (2.8)
35 (4.0)
45 (5.1)
5
17 (1.9)
15 (1.7)
22 (2.5)
7 (.8)
7 (.8)
25 (2.8)
45 (5.1)
45 (5.1)
7 1/2
17 (1.9)
15 (1.7)
22 (2.5)
7 (.8)
7 (.8)
25 (2.8)
45 (5.1)
45 (5.1)
10
17 (1.9)
35 (4.0)
22 (2.5)
7 (.8)
7 (.8)
45 (5.1)
45 (5.1)
45 (5.1)
15
40 (4.5)
175 (19.8)
44 (5)
18 (2)
18 (2)
45 (5.1)
45 (5.1)
50 (5.6)
20
40 (4.5)
175 (19.8)
44 (5)
18 (2)
18 (2)
120 (13.6)
120 (13.6)
50 (5.6)
25
40 (4.5)
175 (19.8)
44 (5)
55 (6.2)
55 (6.2)
120 (13.6)
275 (30.1)
50 (5.6)
30
40 (4.5)
175 (19.8)
44 (5)
70 (7.9)
70 (7.9)
120 (13.6)
275 (30.1)
50 (5.6)
40
200 (22.6)
275 (30.1)
275 (30.1)
375 (42.4)
375 (42.4)
275 (31.1)
N/A
50 (5.6)
50
200 (22.6)
275 (30.1)
275 (30.1)
375 (42.4)
375 (42.4)
275 (31.1)
N/A
50 (5.6)
60
200 (22.6)
275 (30.1)
275 (30.1)
375 (42.4)
375 (42.4)
450 (50.8)
N/A
275 (30.1)
550 to 600 VAC Terminal Tightening Torque
Max. Drive
Output Current
Torque
in-lbs (Nm)
to 11
5 (0.6)
27
17 (1.8)
41
28 (3.0)
77
35 (4.0)
144
100 (11.3)
289
100 (11.3)
Terminal Tightening Torque for Optional
Auxiliary Control Panels
For drives with an optional auxiliary control panel enclosure, tighten
terminal connections in accordance with the tables provided.