46
Function:
This parameter chooses the active resulting reference. If
Hand/Auto
linked reference
is selected, the resulting reference will depend on
whether the drive is in Hand or Auto mode.
The table below shows which reference is active when
Hand/Auto
linked reference
,
Remote reference
or
Local reference
has been
selected. The Hand mode or Auto mode can be selected via the
keypad or by a digital input set in parameters 300 through 307
Digital
Inputs.
Reference Handling
Hand Mode
Auto Mode
Hand/Auto
Local ref. active
Remote ref. active
Remote
Remote ref. active
Remote ref. active
Local
Local ref. active
Local ref. active
Description of choice:
If
Hand/Auto linked reference
is chosen, the motor speed in Hand
mode will be set by the local reference, while in Auto mode it is set by
the remote references and any setpoints selected.
If
Remote reference
is selected, the motor speed will depend on
remote references and any setpoints selected, regardless of whether
Hand mode or Auto mode has been chosen.
If
Local reference
is selected, the motor speed will only depend on the
local reference set via the control panel, regardless of whether Hand
mode or Auto mode has been selected.
204
Minimum Reference
(MIN. REFERENCE)
Value:
If parameter 100,
Configuration = Open loop,
0.000Hz to parameter 205,
Maximum Reference.
✭
0.000 Hz
If parameter 100
Configuration = Closed loop,
parameter 413,
Minimum Feedback,
to
parameter 205,
Maximum Reference.
✭
0.000 Hz
Function:
The
Minimum Reference
sets the minimum value of the sum of all
references. If
Closed loop
has been selected in parameter 100,
Configuration
, the minimum reference is limited by parameter 413,
Minimum Feedback
.
Minimum reference is ignored when the local reference is active. In this
case, minimum reference is determined by parameter 201,
Minimum
Frequency
.
NOTE
For fan applications, factory setting of
parameter 204 is 6 Hz. For pump applications,
factory setting for parameter 204 is 18 Hz.
The unit for the reference can be seen from the following table:
Unit
Parameter 100
Configuration = Open loop
Hz
Parameter 100
Configuration = Closed loop
Par. 415
Description of choice:
Minimum Reference
is the lowest reference value that can be set for
the drive.
205
Maximum Reference
(MAX. REFERENCE)
Value:
If parameter 100,
Configuration = Open loop,
parameter 204,
Minimum Reference
,
to 1000.000 Hz
✭
60.000 Hz
If parameter 100,
Configuration = Closed loop,
parameter 204,
Minimum Reference
, to
parameter 414,
Maximum Feedback
.
✭
60.000 Hz
Function:
The
Maximum Reference
sets the maximum value of the sum of all
references. If
Closed loop
has been selected in parameter 100,
Configuration
, the maximum reference cannot be set above parameter
414,
Maximum Feedback.
The
Maximum Reference
is ignored when
the local reference is active.
The reference unit can be determined from the following table:
Unit
Parameter 100
Configuration = Open loop
Hz
Parameter 100
Configuration = Closed loop
Par. 415
Description of choice:
Maximum reference
is the highest reference value that can be set for
the drive.
✭
I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.