For the analog output, there is a choice of three types of output signal:
0 to 20 mA, 4 to 20 mA or 0 to 32000 pulses. The pulse rate is set by
parameter 322,
Terminal 45, Output, Pulse Scaling
.
See the Electrical Installation, Control Terminals section of this manual
for the ratings of these outputs.
Analog/Digital Outputs
The two analog/digital outputs available through terminals 42 and 45
can be programmed to show a status or an analog value such as
frequency. The status signal is a 24 VDC output.
Analog/Digital Outputs
terminal no.
Analog/Digital Outputs
Terminal Number:
42
45
Parameter:
319
321
Value:
No function (NO FUNCTION)
[0]
[0]
Drive ready (READY)
[1]
[1]
Standby (ENABLED & NO WARNING)
[2]
[2]
Running (RUNNING)
[3]
[3]
Running at ref. value (RUNNING AT REFERENCE)
[4]
[4]
Running, no warning (RUNNING NO WARNING)
[5]
[5]
Local reference active (DRIVE IN LOCAL REF.)
[6]
[6]
Remote controlled references active (DRIVE IN REMOTE REF.)
[7]
[7]
Alarm (ALARM)
[8]
[8]
Alarm or warning (ALARM OR WARNING)
[9]
[9]
No alarm (NO ALARM)
[10]
[10]
Current limit (CURRENT LIMIT)
[11]
[11]
Safety interlock (SAFETY INTERLOCK)
[12]
[12]
Start command active (START SIGNAL APPLIED)
[13]
[13]
Reversing (RUNNING IN REVERSE)
[14]
[14]
Thermal warning (THERMAL WARNING)
[15]
[15]
Hand mode active (DRIVE IN HAND MODE)
[16]
[16]
Auto mode active (DRIVE IN AUTO MODE)
[17]
[17]
Sleep mode (SLEEP MODE)
[18]
[18]
Output frequency lower than parameter 223 (F OUT < F LOW)
[19]
[19]
Output frequency higher than parameter 223 (F OUT > F HIGH)
[20]
[20]
Out of frequency range (FREQ. RANGE WARN.)
[21]
[21]
Output current lower than low current, parameter 221 (I OUT < I LOW)
[22]
[22]
Output current higher than high current, parameter 222 (I OUT > I HIGH)
[23]
[23]
Out of current range (CURRENT RANGE WARN)
[24]
[24]
Out of feedback range (FEEDBACK RANGE WARN.)
[25]
[25]
Out of reference range (REFERENCE RANGE WARN)
[26]
[26]
Relay 123 (RELAY 123)
[27]
[27]
Input phase loss (MAINS PHASE LOSS)
[28]
[28]
Output frequency, (OUT. FREQ. 0-20 mA)
[29]
[29]
Output frequency, (OUT. FREQ. 4-20 mA)
[30]
★
[30]
Output frequency (pulse sequence), (OUT. FREQ. PULSE)
[31]
[31]
External reference, (EXT. REF. 0-20 mA)
[32]
[32]
External reference, (EXTERNAL REF. 4-20 mA)
[33]
[33]
External reference (pulse sequence), (EXTERNAL REF. PULSE)
[34]
[34]
Feedback, (FEEDBACK 0-20 mA)
[35]
[35]
Feedback, (FEEDBACK 4-20 mA)
[36]
[36]
Feedback (pulse sequence), (FEEDBACK PULSE)
[37]
[37]
Output current, 0-20 mA (MOTOR CUR. 0-20mA)
[38]
[38]
Output current, 4-20 mA (MOTOR CUR. 4-20mA)
★
[39]
[39]
Output current (pulse sequence), (MOTOR CUR PULSE)
[40]
[40]
Output power, 0-20 mA (MOTOR POWER 0-20mA)
[41]
[41]
Output power, 4-20 mA (MOTOR POWER 4-20mA)
[42]
[42]
Output power (pulse sequence), 0- 32000 pulses (MOTOR POWER PULSE)
[43]
[43]
Controlled by serial bus: 0-20 mA (BUS CONTROL 0-20MA)
[44]
[44]
Controlled by serial bus: 4-20 mA (BUS CONTROL 4-20MA)
[45]
[45]
Controlled by serial bus: pulses (BUS CONTROL PULSE)
[46]
[46]
✭
I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.