117
RTAA-IOM-3
Table 18
Diagnostics and Troubleshooting Chart (Continued)
DIAG. ACTIVE
CODE DIAGNOSTIC DESCRIPTION
TYPE
MODES
CAUSE
1d3
Comp. Suction Temp. Sensor -
CMR
All
a . Open or Short in sensor electrical
Circuit 1
circuitry.
1d4
Comp. Suction Temp. Sensor -
CMR
All
a. Open or Short in sensor electrical
Circuit 2
circuitry.
1d7
Phase Reversal Protection Lost -
CMR
Compressor Energized to
a. The phase reversal protection
Compressor A
To Transition Command
Compressor A has become
inoperative. The phase rotation
protection system failed to detect two
in a row of one of the four phase
circuit states; Phase reversal, Phase
Rotation OK, Phase A lost, Phase B
lost.
1d8
Phase Reversal Protection Lost -
CMR
Compressor Energized to
Same as diagnostic 1d7.
Compressor B
Transition Command
1d9
Phase Reversal Protection Lost -
CMR
Compressor Energized to
Same as diagnostic 1d7.
Compressor C
Transition Command
1dA
Phase Reversal Protection Lost -
CMR
Compressor Energized to
Same as diagnostic 1d7.
Compressor D
Transition Command
1db
Slaved EXV Elec. Drive Circuit -
CMR
On Demand and
a. Wiring between the EXV and the UCM
Refrigerant Circuit I
Pre-Start is “Open”. Check the
connector for proper termination.
b. EXV motor is faulty.
c. EXV drive circuits on Module 1U3 are
faulty
1dC
Slaved EXV Elec. Drive Circuit
CMR
On Demand and
Same as diagnostic 1db. Also refer to
Refrigerant Circuit 2
Pre-Start
diagnostics 1A9 and 1AA.
412
1U1 Indicating
IFW
All
The 1U1 Module has detected a loss of
1U2 Communications
inter-processor communications from
the 1U2 Module.
413
1U1 Indicating
MMR
All
The 1U1 Module has detected a loss of
1U3 Communications
inter-processor communications from
the 1U3 Module.
414
1U1 Indicating
CMR
All
The 1U1 Module has detected a loss of
1U4 Communications
inter-processor communications from
the 1U4 Module.
415
1U1 Indicating
CMR
All
The 1U1 Module has detected a loss of
1U5 Communications
inter-processor communications from
the 1U5 Module.
416
1U1 Indicating
CMR
All
The 1U1 Module has detected a loss of
1U6 Communications
inter-processor communications from
the 1U6 Module.
417
1U1 Indicating
CMR
All
The 1U1 Module has detected a loss of
1U7 Communications
inter-processor communications from
the 1U7 Module.
418
1U1 Indicating
CMR
All
The 1U1 Module has detected a loss of
1U8 Communications
inter-processor communications from
the 1U8 Module.
431
1U3 Indicating
MMR
All
The 1U3 Module has detected a loss of
1U1 Communications
inter-processor communications from
the 1U1 Module.
434
1U3 Indicating
CMR
All
The 1U3 Module has detected a loss of
1U4 communications
inter-processor communications from
the 1U4 Module.
Summary of Contents for RTAA-130
Page 2: ... American Standard Inc 1991 ...
Page 8: ...8 RTAA IOM 3 ...
Page 24: ...24 RTAA IOM 3 ...
Page 50: ...50 RTAA IOM 3 Figure 30 Refrigerant Circuit Identification ...
Page 52: ...52 RTAA IOM 3 Figure 31 Remote Evaporator Piping Example ...
Page 59: ...59 RTAA IOM 3 Continued from Previous Page See Notes on Next Page ...
Page 63: ...63 RTAA IOM 3 Continued from Previous Page See Notes on Page 61 ...
Page 65: ...65 RTAA IOM 3 Continued from Previous Page See Notes on Page 61 ...
Page 76: ...76 RTAA IOM 3 ...
Page 92: ...92 RTAA IOM 3 Figure 51 Operator Interface Controls ...
Page 120: ...120 RTAA IOM 3 ...
Page 127: ...127 RTAA IOM 3 Continued from Previous Page 2307 1566C ...
Page 128: ...128 RTAA IOM 3 Figure 57 Unit Sequence of Operation RTAA 130 to 200 Tons 2306 9122A ...
Page 132: ...132 RTAA IOM 3 Figure 58 Operator s Log ...
Page 138: ...138 RTAA IOM 3 ...