A. The line sizes established in this
installation manual are to be used only
for 40-50 F leaving water temperature
and full-load ice-making applications.
B. The evaporator can be mounted
only on the SAME PLANE OR LOWER
PLANE than the outdoor unit. Figure 28
illustrates what not to do. The elevation
difference is to not exceed 100 feet.
C. Piping between evaporator and
outdoor unit is to not exceed 200
(linear) feet or an equivalent length
(includes equivalent length pressure
drop of fittings) of 300 feet.
D. The suction line must never cross or
be above a plane that is 1’8" above the
bottom of the outdoor unit. Figure 29
illustrates what not to do.
Figure 27
Remote Evaporator Installation –
Condenser and Compressor
above Evaporator
Summary of Contents for RTAA-130
Page 2: ... American Standard Inc 1991 ...
Page 8: ...8 RTAA IOM 3 ...
Page 24: ...24 RTAA IOM 3 ...
Page 50: ...50 RTAA IOM 3 Figure 30 Refrigerant Circuit Identification ...
Page 52: ...52 RTAA IOM 3 Figure 31 Remote Evaporator Piping Example ...
Page 59: ...59 RTAA IOM 3 Continued from Previous Page See Notes on Next Page ...
Page 63: ...63 RTAA IOM 3 Continued from Previous Page See Notes on Page 61 ...
Page 65: ...65 RTAA IOM 3 Continued from Previous Page See Notes on Page 61 ...
Page 76: ...76 RTAA IOM 3 ...
Page 92: ...92 RTAA IOM 3 Figure 51 Operator Interface Controls ...
Page 120: ...120 RTAA IOM 3 ...
Page 127: ...127 RTAA IOM 3 Continued from Previous Page 2307 1566C ...
Page 128: ...128 RTAA IOM 3 Figure 57 Unit Sequence of Operation RTAA 130 to 200 Tons 2306 9122A ...
Page 132: ...132 RTAA IOM 3 Figure 58 Operator s Log ...
Page 138: ...138 RTAA IOM 3 ...