19
Installation
Table 1
Typical Unit Weights & Point Loading Data
Unit
Condenser
Operating
Operating Weight Distribution @ Unit Mounting Points
Size
Fin Mat’l.
Weight
1
2
3
4
5
6
C20
Alum.
1870
595
470
470
335
—
—
Copper
2085
690
475
490
430
—
—
C25
Alum.
2085
700
470
490
425
—
—
Copper
2370
760
540
580
490
—
—
C30
Alum.
3060
865
430
725
340
430
270
Copper
3450
875
525
830
385
555
280
C40
Alum.
3290
560
580
580
595
480
495
Copper
3680
570
755
605
540
640
570
C50
Alum.
3900
685
715
720
750
505
525
Copper
4435
840
870
660
680
680
705
C60
Alum.
4885
885
820
855
985
620
720
Copper
5820
935
1220
875
920
1010
860
Notes:
1. Mounting locations correlate with those shown in point loading illustration.
2. Operating weight includes refrigerant, oil and water.
3. Shipping weight includes refrigerant and oil charges.
Figure 3
Rigging and Center-of-Gravity Data
WARNING
Heavy Objects!
Do not use cables (chains or slings) except as shown.
Each of the cables (chains or slings) used to lift the
unit must be capable of supporting the entire weight of
the unit. Lifting cables (chains or slings) may not be of
the same length. Adjust as necessary for even unit lift.
Other lifting arrangements may cause equipment or
property-only damage. Failure to properly lift unit could
result in death or serious injury. See details below.
Note: Use spreader bars as shown in the diagram.
Refer to the Installation manual or nameplate for
unit weight. Refer to the Installation instructions
located inside the control panel for further rigging
information.
Shipping
Center of Gravity
Unit
Weight
X
Z
Size
(Max. Lbs.)
Inches mm
Inches mm
C20
1875
39" 991
26" 660
C25
2085
40" 1016
26" 660
C30
3065
37" 940
30" 762
C40
3290
42" 1067
45" 1143
C50
3900
52" 1321
45" 1143
C60
4865
54" 1372
46" 1168
Summary of Contents for IntelliPak CG-SVX02B-EN
Page 10: ...10 General Information Module Mounting Locations Screw Hole...
Page 12: ...12 Figure 1 Typical Installation Clearances for Single Multiple or Pit Applications...
Page 13: ...13 Figure 2 C20 Ton Unit Dimensional Data Recommended Clearances...
Page 14: ...14 Figure 2 C25 Ton Unit Dimensional Data Recommended Clearances...
Page 15: ...15 Figure 2 C30 Ton Unit Dimensional Data Recommended Clearances...
Page 16: ...16 Figure 2 C40 Ton Unit Dimensional Data Recommended Clearances...
Page 17: ...17 Figure 2 C50 Ton Unit Dimensional Data Recommended Clearances...
Page 18: ...18 Figure 2 C60 Ton Unit Dimensional Data Recommended Clearances...
Page 35: ...35...
Page 36: ...36 Figure 12B Typical GBAS 0 5 Volt Connections Diagram...
Page 37: ...37...
Page 38: ...38...
Page 63: ...63...
Page 64: ......