Sequence of Operation
OAU-SVX006E-EN
81
Single Zone VAV Control
After completing the starting sequence, the unit adjusts
supply fan speed to maintain
Space Temperature Active
to
Space Temperature Setpoint Active
. When the unit is in
Dehumidification Mode
, the unit adjusts the supply fan
speed to maintain the
Space Dewpoint
to the
Space
Dewpoint Calculated Enable Setpoint
.
Supply fan speed is limited between
Supply Air Flow
Minimum Setpoint Active
and
Supply Air Flow Maximum
Setpoint
(both factory set).
Field Enabled Space Pressure Control
Units ordered as constant volume can be field enabled to
control the supply fan speed to a pressure input.
Duct
Static Pressure Local
must be put In Service, configured,
and referenced to an open input using Tracer TU. The
program will automatically adjust supply fan speed to
maintain
Duct Static Pressure Setpoint BAS
.
Economizer Mode
Economizer Mode
is enabled when the
Outdoor Air
Enthalpy
falls below Return Air Enthalpy and the
Outdoor
Air Temperature Active
is below 80°F.
Economizer Mode
continues with a deadband of 3 BTU/lb, and 1°F for
temperature. If the unit is not in
Free Cooling Mode
during
Economizer Mode
, the unit opens the outdoor air damper
to the
Outdoor Air Damper Maximum Position Setpoint
.
Mechanical cooling will not be locked out unless the unit
is in
Free Cooling Mode
.
Refer to Multi-State Value
Economizer System
Status
to
determine the active status for the economizing.
Free Cooling Mode
is enabled when the unit is in
Economizer Mode
and the
Outdoor Air Temperature
Active
is cooler than five degrees below the
Discharge Air
Temperature Setpoint Active
. During
Free Cooling Mode
,
mechanical cooling is locked out and the unit adjusts the
outdoor air damper position to maintain the
Discharge Air
Temperature Setpoint Active
.
Ventilation Mode
Discharge Air Control
Ventilation Mode
is enabled when the
Outdoor Air
Temperature Active
is between the
Outdoor Air Cooling
Enable Setpoint
and the
Outdoor Air Heating Enable
Setpoint
. During
Ventilation Mode
, heating and cooling is
locked out and the unit supplies un- conditioned air.
Ventilation Mode
is locked out whenever the unit is in
Dehumidification Mode
.
Multi-Zone VAV Control
Ventilation Mode
locked out.
Space Control
Ventilation Mode
is enabled when the
Outdoor Air
Temperature Active
and the
Space Temperature Active
is
within two degrees of the
Space Temperature Setpoint
Active
. During
Ventilation Mode
, heating and cooling is
locked out and the unit supplies un- conditioned air.
Ventilation Mode
is locked out whenever the unit is in
Dehumidification Mode
.
Single Zone VAV Control
Ventilation Mode
is enabled when the
Outdoor Air
Temperature Active
and the
Space Temperature Active
is
within two degrees of the
Space Temperature Setpoint
Active
. During
Ventilation Mode
, heating and cooling is
locked out, the supply fan goes to minimum air flow, and
the unit supplies un-conditioned air.
Ventilation Mode
is
locked out whenever the unit is in
Dehumidification Mode
.
Primary Heating Mode
Discharge Air Control
Heating Mode is enabled whenever the
Outdoor Air
Temperature Active
is below the
Outdoor Air Heating
Enable Setpoint
. During Heating Mode,
Heat Capacity
is
adjusted to maintain the
Discharge Air Temperature Local
to
Discharge Air Temperature Setpoint Active
.
Multi-Zone VAV Control
Heating Mode is enabled according to the graph shown in
. Using the graph, setpoint is
Discharge Air
Temperature Setpoint Active
, offset is 2°F, and
temperature is
Discharge Air Temperature Local
.
Dehumidification Mode
takes priority over Heating Mode.
During Heating Mode,
Heat Capacity
is adjusted to
maintain the
Discharge Air Temperature Local
to
Discharge Air Temperature Setpoint Active
.
Space Control or Single Zone VAV Control,
with Energy Recovery Wheel or has Mixed
Air
Heating Mode is enabled according to the graph shown in
. Using the graph, setpoint is
Space
Temperature Setpoint Active
, offset is
Occupied Offset
,
and temperature is
Space Temperature Active
.
Dehumidification Mode
takes priority over Heating and
Cooling Mode. During Heating Mode,
Heat Capacity
is
adjusted to maintain the
Discharge Air Temperature Local
to
Discharge Air Temperature Setpoint Active
.