Sequence of Operation
OAU-SVX006E-EN
83
Space Control or Single Zone VAV Control,
with Energy Recovery Wheel or has Mixed
Air
Cooling Mode is enabled according to the graph shown in
. Using the graph, setpoint is Space
Temperature Setpoint Active, offset is Occupied Offset,
and temperature is
Space Temperature Active
.
Dehumidification Mode
takes priority over Cooling Mode.
Space Control or Single Zone VAV Control
with No Energy Recovery Wheel and 100%
Outdoor Air
Cooling Mode is enabled whenever the
Outdoor Air
Temperature Active
rises above the
Outdoor Air Cooling
Enable Setpoint
. When this occurs, heating is not allowed,
regardless of space conditions.
When the
Outdoor Air Temperature Active
is above the
Outdoor Air Heating Enable
, but below the
Outdoor Air
Cooling Enable Setpoint
, Cooling Mode is enabled
according to the graph shown in
. Using
the graph, setpoint is
Space Temperature Setpoint Active
,
offset is
Occupied Offset
, and temperature is
Space
Temperature Active
.
Compressor Low Ambient Lockout
On units without head pressure control, the compressors
will be locked out if the
Outdoor Air Temperature Active
falls below the
Compressor Low Ambient Lockout
Setpoint
and there is a demand for cooling. When this
occurs, the unit will display
Compressor Low Ambient
Lockout Active
as an informational diagnostic.
Evaporator Frost Protection
Circuit 1 refrigeration pressure is monitored, and
Cooling
Capacity
will be limited to prevent the indoor coil from
freezing. If the unit has digital scroll on the second circuit,
then both circuits will be monitored.
Dehumidification Mode
Outdoor Air Dewpoint
is calculated using
Outdoor Air
Temperature Active
and
Outdoor Air Humidity Active
.
For
Dehumidification Temperature Active
, OAN Rev. 6
(OANG) cabinet uses
Discharge Air Dewpoint
(calculated
using
Discharge Air Temperature Local
and
Discharge Air
Humidity Local
), all other cabinets use
Indoor Coil Leaving
Air Temperature Local
.
Discharge Air Control
Dehumidification Mode
is enabled whenever the
Outdoor
Air Dewpoint
rises above the
Outdoor Air Dewpoint
Enable Setpoint
. The
Outdoor Air Temperature Active
must be above
Outdoor Air Heating Enable Setpoint
.
During
Dehumidification Mode, Cooling Capacity
is
adjusted to maintain the
Dehumidification Temperature
Setpoint Active
, which is written to by
Dehumidification
Temperature Setpoint
(adjustable).
Hot Gas Reheat Valve
Command
(if installed) is adjusted to maintain
Discharge
Air Temperature Setpoint Active
.
Multi-Zone VAV Control
Dehumidification Mode
is enabled whenever the
Outdoor
Air Dewpoint
rises above the
Outdoor Air Dewpoint
Enable Setpoint
.
During
Dehumidification Mode
,
Cooling Capacity
is
adjusted to maintain the
Dehumidification Temperature
Setpoint Active
, which is written to by
Dehumidification
Temperature Setpoint
(adjustable).
Hot Gas Reheat Valve
Command
(if installed) is adjusted to maintain
Discharge
Air Temperature Setpoint Active
.
Space Control with Energy Recovery
Wheel or has Mixed Air
Dehumidification Mode
is enabled whenever the
Space
Dewpoint
rises above the
Space Dewpoint Calculated
Enable Setpoint.
During
Dehumidification Mode
, the
Dehumidification
Temperature Setpoint Active
is reset by comparing
Space
Dewpoint
to
Space Dewpoint Calculated Enable Setpoint
minus 2°F.
Hot Gas Reheat Valve Command
(if installed) is
adjusted to maintain
Discharge Air Temperature Setpoint
Active
.
Space Control with No Energy Recovery
Wheel and 100% Outdoor Air
Dehumidification Mode
is enabled whenever the
Space
Dewpoint
rises above the
Space Dewpoint Calculated
Enable Setpoint
, or when the
Outdoor Air Dewpoint
rises
above the
Outdoor Air Dewpoint Enable Setpoint
.
During
Dehumidification Mode
, the
Dehumidification
Temperature Setpoint Active
is reset by comparing
Space
Dewpoint
to
Space Dewpoint Calculated Enable Setpoint
minus 2°F.
Hot Gas Reheat Valve Command
(if installed) is
adjusted to maintain
Discharge Air Temperature Setpoint
Active
.
Hot Gas Reheat Purge
Hot Gas Reheat Purge Mode
is initiated if the
Hot Gas
Reheat Valve Command
is between 10% and 50% for thirty
continuous minutes. During
Hot Gas Reheat Purge Mode
the signal first goes to 80% for one minute, then to 10% for
one minute. The
Hot Gas Reheat Valve Command
returns
to its previous position and will begin to modulate after a
30-second delay.
Supplemental Electric Reheat (Not
Included in Standard Operation)
If the
Hot Gas Reheat Valve Command
is at 100%, the SCR
electric heat is enabled
Heat Capacity
at 0%. If
Heat
Capacity
rises above 0%, the
Hot Gas Reheat Valve
Command
will be locked at 100% and the electric heat will