System Configuration and Pre-Start
OAU-SVX006E-EN
49
MV-10
Supply Fan Wheel Size
–
Factory set supply fan size.
MV-11
Direct Fired Burner Size
–
Factory set direct fired burner size.
MV-12
Exhaust Fan Wheel Size
–
Factory set exhaust fan size.
MV-13
Program Control Type
●
#N/A
1 = Space Control
2 = Discharge Control 3 = Single Zone VAV 4 =
Multi Zone VAV
5 = Critical Space Control
6 = Critical Discharge Control
MV-16
Dehumidification
System Status
1 = Off
2 = On
MV-17
Economizer System
Status
1 = Not Economizing 2 = Economizer Mode
3 = Free Cooling Mode
4 = Ventilation Mode
MV-19
Compressor 1 Status
Active
1 = Disabled
2 = Enabled, No Running Status 3 = Enabled With
Running Status 4 = Enabled, No VFD Alarm
5 = Not Installed
MV-20
Compressor 2 Status
Active
1 = Disabled
2 = Enabled, No Running Status 3 = Enabled With
Running Status 4 = Not Installed
5 = Input Status In Fail
MV-21
Compressor 3 Status
Active
See Compressor 2 Status Active MV-20
MV-23
Compressor 4 Status
Active
See Compressor 2 Status Active MV-20
MV-24
Compressor 5 Status
Active
See Compressor 2 Status Active MV-20
MV-25
Compressor 6 Status
Active
See Compressor 2 Status Active MV-20
Table 8.
Chart of analog and binary input/output (continued)
#
BACnet Point Name
Write
Default
Range
Units
Description