WSHP-SVX014F-EN
Figure 30.
UC400 controls with DIP switch settings
Table 29.
Profiles for altitude range
Profile
Altitude (Feet)
A
0–2000
B
2000–4000
C
4000–6000
D
Above 6000
Vertical - Units with Deluxe 24V or
Tracer
®
®
ZN524 controls
For vertical sizes EXVG 009-070 and DXVG 024-070, the
ECM is programmed for constant torque and delivers
airflow similar to a PSC motor while operating at a
higher efficiency.
Figure 31.
ECM control box
Figure 32.
ECM control board
1. Potentiometer will be used to adjust the PWM
output
2. Seven segment display
Using a screwdriver, the potentiometer will be used to
adjust the PWM output from 20% to 100% PWM.
Increasing the PWM will increase the motor speed.
When setting the airflow for air balancing, the high-
speed terminal (GH) must have 24 Vac signal. This will
ensure that the PWM output will be adjusted for the full
load airflow.
The display will show the commanded motor speed
percentage. If running on low speed (GL), the low-
speed value will be displayed. If running in GH the
high-speed value will be displayed. If both GH and GL
input signals are present, the PWM output value will be
the GH value.
Waterside Economizer
Installation
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..