Table 40.
Cooling water pressure drop (WPD) in feet
of head for EX* units (continued)
Unit Size
(60 Hz)
EWT °F
GPM
Ft.
Pressure
EXHF015
86
3.5
5.4
EXHF018
86
4.2
4.1
EXHF024
86
5.6
6.1
EXHF030
86
7.0
9.2
EXHF036
86
8.4
5.5
EXHF042
86
9.8
7.8
EXHF048
86
11.2
8.2
EXHF060
86
14.0
7.2
EXHF070
86
15.4
6.3
EXVG009
86
2.3
3.4
EXVG012
86
3.0
5.9
EXVG015
86
3.8
8.2
EXVG018
86
4.5
1.9
EXVG024
86
6.0
3.0
EXVG030
86
7.5
4.1
EXVG036
86
9.0
5.8
EXVG042
86
10.5
4.9
EXVG048
86
12.0
5.9
EXVG060
86
15.0
10.6
EXVG070
86
17.5
9.3
Table 41.
Heating water pressure drop (WPD) in feet
of head for DX* units
Unit Size
EWT °F
GPM
Ft.
Pressure
DXHF024
65
5.6
6.6
DXHF036
65
8.4
5.8
DXHF048
65
11.2
9.0
DXHF060
65
14.0
7.4
DXHF070
65
15.4
6.6
DXVG024
68
6.0
3.3
DXVG036
68
9.0
6.3
DXVG048
68
12.0
6.6
DXVG060
68
15.0
12.0
DXVG070
68
17.5
10.0
Table 42.
Heating water pressure drop (WPD) in feet
of head for EX* units
Unit Size
(60 Hz)
EWT °F
GPM
Ft.
Pressure
EXHF006
68
1.8
4.2
EXHF009
68
2.1
3.9
EXHF012
68
2.8
4.1
EXHF015
68
3.5
5.7
EXHF018
68
4.2
5.0
EXHF024
68
5.6
7.9
EXHF030
68
7.0
11.2
EXHF036
68
8.4
6.5
EXHF042
68
9.8
9.4
EXHF048
68
11.2
9.4
EXHF060
68
14.0
7.1
EXHF070
68
15.4
7.2
EXVG009
68
2.3
3.7
EXVG012
68
3.0
6.4
EXVG015
68
3.8
8.8
EXVG018
68
4.5
2.0
EXVG024
68
6.0
3.2
EXVG030
68
7.5
4.5
EXVG036
68
9.0
6.1
EXVG042
68
10.5
5.1
EXVG048
68
12.0
6.2
EXVG060
68
15.0
11.4
EXVG070
68
17.5
9.9
Water Volume
The information below is provided for use in
calculating glycol requirements for the unit.
Table 43.
Water volume for DX* units
Unit Size
Water Side
Volume
(in
3
)
Water Side
Volume
(ft
3
)
Water Side
Volume
(gallons)
DXHF024
89.8
0.052
0.389
DXHF036
171.2
0.099
0.741
DXHF048
200.8
0.116
0.869
DXHF060
331.2
0.192
1.434
DXHF070
331.2
0.192
1.434
DXVG024
118.6
0.069
0.513
DXVG036
118.6
0.069
0.513
DXVG048
196.5
0.114
0.851