52
WSHP-SVX014F-EN
Table 34.
Electrical data - 2 to 6 tons, DX*024-070 (continued)
Model
No.
Unit
Volts
Total
Unit FLA
Comp
RLA
Comp
LRA
Blower
Motor FLA
Blower
Motor
HP
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
Electric
Heat kW
Electric
Heat
Amps
DXVG060
208-230/
60/1
25.0
21.2
104.0
3.8
1
31/31
50/50
0.0
0.0
DXVG060
208-230/
60/3
17.8
14.0
83.1
3.8
1
22/22
35/35
0.0
0.0
DXVG060
460/60/3
8.3
6.4
41.0
1.9
1
10
15
0.0
0.0
DXVG070
208-230/
60/1
31.9
26.9
139.9
5.0
1
39/39
60/60
0.0
0.0
DXVG070
208-230/
60/3
21.5
16.5
110.0
5.0
1
26/26
40/40
0.0
0.0
DXVG070
460/60/3
9.7
7.2
52.0
2.5
1
12
15
0.0
0.0
Table 35.
Electrical data - minimum and maximum
Digit 8
Rated Voltage
Hz
Ph
Minimum Utilization
Voltage
Maximum Utilization
Voltage
1
208
60
1
197
229
2
230
60
1
207
253
3
208
60
3
187
229
4
460
60
3
414
506
7
265
60
1
239
292
8
230
60
3
207
253
A
208-230
60
1
197
253
B
208-230
60
3
187
253