4. „Next“ leads you to a new dialog. Type in the specific fields the name of the PLC device and choose the
used PLC in the driver selection (e.g. „SIMATIC S7 – 300/400 V6.0“).
5. Via „Parameter…“ you are calling an configuration dialog from the chosen PLC driver Set up the station
address of the panel (example „1“) and of the PLC (example „2“). Leave the point “Interface” in the
standard configuration. In the sector „Net parameter“ choose the interface which uses your module on the
PLC (e.g. „MPI“). Configure the baud rate to „187.5“.
6. The button „More …“ leads you to a small dialog where the „Highest Station Address“ should be
configured to „126“. Set up the „Number of masters“ (e.g. „1“)
7. confirm with „OK“ until you got back to the „Control Selection“.Go on with „Next“. 8. In the main window
start the Transfer Settings dialog by clicking on „File“ „Transfer“ „Settings…“. Choose „MPI / PROFIBUS DP“
from the listbox and type in the station address of the operator panel (e.g. „1“). Confirm with „OK“. and
start with your work If you have finished working on this project you can go on with the next steps.