Installation
31
Installing an air baffle
To install an air baffle:
1.
Position the air baffle over the chassis. Align it with the slits on the top of the fan cage. Make sure the
air baffle does not touch the DIMM modules during the installation procedure.
CAUTION:
To avoid damaging server components, do not use force when installing the air
baffle. Be sure that all DIMM latches are locked to avoid damaging the components.
2.
Lower the air baffle into the chassis, and gently press down on the front of the ari baffle to ensure the
tabs on the air baffle are inserted through the slits on the fan cage.
3.
Install the accesspanel (on page 29).