Chapter 5 Function parameter
56
0
Running frequency
0 to maximum output frequency
1
Set frequency
0 to maximum output frequency
2
Output current
0 to 2 times of rated inverter current
3
Output torque
0 to 2 times of rated motor current
4
Output power
0 to 2 times of rated power
5
Output voltage
0 to 1.2 times of rated inverter voltage
6
AI1 analog input value
0 to 10V/0 to 20mA
7
AI2 analog input value
0 to 10V/0 to 20mA
8
Running speed
0 to 2 times rated motor speed
F2.05 AO1 output lower limit
0.0% to F2.07
0.0%
☆
F2.06
Lower limit corresponds to
AO1 output
0.00V to 10.00V
0.00V
☆
F2.07 AO1 output upper limit
F2.05 to 100.0%
100.0%
☆
F2.08
Upper limit corresponds to
AO1 output
0.00V to 10.00V
10.00V
☆
The above function code defines the relationship between output value and analog
output, when output value is out of the set maximum output or minimum output, the
maximum output or the minimum output will be used for calculation.
When the analog output is the current output, 1mA current is equivalent to 0.5V
voltage.
In the different applications, the 100% of analog output value can be different,
please refer to the description of each application for details.
AO
10V( 20mA)
对应设定
100%
0. 0%
Relationship diagram between analog output and set amount
F2.09 MO1 Turn-on delay time
0.0~3600s
0.0s
☆
F2.10 MO1 Turn-off delay time
0.0~3600s
0.0 s
☆
F2.11 Turn-on delay time of relay
0.0~3600s
0.0 s
☆
F2.12 Turn-off delay time of relay
0.0~3600s
0.0 s
☆
function code is defined as the corresponding delay time of the level change from
Corresponding
setup
Chapter 5 Function parameter
57
output terminal opens and then disconnects.
F2.13 Reserved
F2.14
DO output terminal active
status selection
0x00 to 0x1F
00
☆
This function code is used to set the polarity of the input terminals. When the bit is
set to 0, the polarity of output terminal is positive; when the bit is set to 1, the polarity
of output terminal is negative.
Bit0
Bit1
Bit2
Bit3
Bit4
MO1
Reserved
Reserved
R0
Reserved
F2.15 MO1 output type selection
0: pulse output
1: digital output
☆
M01 is the reuse programmable terminal, it can be pulse out terminal as well as
open collector digital output terminal
As a pulse output, the maximum frequency of output pulse is 10kHz, see detailed
information from F2.16.
F2.16 MO1 pulse output selection
0: running frequency
1: set frequency
2: output current
3: output torque
4: output power
5: output voltage
6: AI1 input value
7: AI2 input value
8:running
speed/RPM
9
~
10: reserved
☆
M01 pulse output frequency range is 0.01kHz-F2.20 (maximum output pulse
value), output pulse set according to F2.17-F2.20, see relative output pulse range from
F2.04.
F2.17
MO1 lower limit of output
pulse
0.0%
~
F2.19
0.0%
☆
F2.18
Lower limit corresponding
M01 pulse output
0.1-10kHz
0.0kHz
☆
F2.19
Higher limit of M01 pulse
output
F2.17-100%
100%
☆
F2.20
Higher limit corresponding
M01 pulse output
0.1-10kHz
10kHz
☆
When pulse output value exceed maximum or minimum output range, will
calculate based on output higher limit or lower limit, adjust parameters through F2.17-
F2.20.
Summary of Contents for CA-203A
Page 1: ...Vector control inverter Operating manual CA Series www tpg tw com...
Page 61: ...1 TPG Corp TPG Corp 1 1 1 1 1 1 1 1 1 2 1 2...
Page 62: ...2 1 2 U V W EMC P RB R S T U V W 3 U V W AC36V 1 3 1 500V 5M 2 3 0Hz 400Hz 50Hz 4 5 PWM...
Page 70: ...18 4 7 CA Series K1 K1 K1 R S T MC1 MC2 MC1 MC2 M 3 4 5 19 4 8 4 6 R S T...
Page 101: ...80 7 1 3 7 3 81 8 1 6 LED OLED 2 1 R S T U V W IGBT 8 2...
Page 109: ...MODBUS 05H 06H 07H 08H EPPROM...