Chapter 5 Function parameter
70
point of momentary
power failure
voltage)
F8.10 Frequency fall rate of
momentary power failure
0.00Hz/s to F0.08 (maximum
output frequency)
0.00Hz/s
☆
5-2-11.F9 Group - Communication parameter group
Code
Parameter name
Setting range
Factory
default
Change
1200bps
0
2400bps
1
4800bps
2
9600bps
3
19200bps
4
F9.00
Communication
baud rate setting
38400bps
5
3
☆
This parameter is used to set the data transfer rate between the host computer and
the inverter. Note: the baud rate must be set to the same for the host computer and the
inverter, otherwise communication can not be achieved. The larger baud rate, the faster
communication speed.
F9.01
Data bits parity
settings
0: no parity (N, 8, 1) for RTU
1: even parity (E, 8, 1) for RTU
2: odd parity (O, 8, 1) for RTU
3: no parity (N, 8, 2) for RTU
4: even parity (E, 8, 2) for RTU
5: odd parity (O, 8, 2) for RTU
6: no parity (N, 7, 1) for ASCII
7: even parity (E, 7, 1) for ASCII
8: odd parity (O, 7, 1) for ASCII
9: no parity (N, 7, 2) for ASCII
10: even parity (E,7,2) for ASCII
11: odd parity (O,7,2) for ASCII
12: no parity (N,8,1) for ASCII
13: even parity (E,8,1) for ASCII
14: odd parity (O,8,1) for ASCII
15: no parity (N,8,2) for ASCII
16: even parity (E,8,2) for ASCII
17: odd parity (O,8,2) for ASCII
1
☆
Note: the set data for the host computer and the inverter must be the same.
F9.02
Communication
address of this unit
1 to 247, 0 for broadcast address
1
☆
Chapter 5 Function parameter
71
When the master is in the write-frame, the communication address of the slave is
set to 0, that is the broadcasting communication address, all slaves on MODBUS will
accept the frame, but the slave does not respond. Note that the slave's address can not
be set to 0.
The communication address of this unit has uniqueness in the communication
network, which is the basis of peer-to-peer communication for the host computer and
the inverter.
F9.03
Communication
response delay
0 to 200ms
5ms
☆
Response delay: it refers to the interval time from the end of the inverter receiving
data to the start of it sending response data to the host machine. If the response delay is
less than the system processing time, then the response delay time is subject to the
system processing time; If the response delay is longer than the system processing
time, after the system finises the data processing, and continues to wait until the
response delay time, and then sends data to the host computer.
F9.04
Communication
timeout fault time
0.0 (invalid) ; 0.1 to 100.0s
0.0 s
☆
Communication time-out parameter is not valid when the function code is set to
0.0s.
When the function code is set to valid, if the interval time between one
communication and the next communication exceeds the communication time-out time,
the system will report communication failure error (E.CE) .
Generally, it is set to invalid. If the parameter can be set to monitor the
communication status in continuous communication system.
F9.05
Data transfer format
selection
0: non-standard MODBUS protocol
1: standard MODBUS protocol
2: ASCII
0
☆
Alarm and free stop
0
No alarm and continue to run
1
No alarm and stop at the
selected mode
(Communication control mode
only)
2
F9.06
Transmission error
handling
1: No alarm and stop at the
selected mode
(All control mode)
3
1
☆
In exceptional circumstances, the inverter can shield E.CE fault, stop or contiune
running by setting the action of handling communication error.
F9.07
Transmission
response handling
0: Write operations responded
1: Write operations not responded
0
☆
When units digit of the function code LED is 0, the host computer of inverter responds
Summary of Contents for CA-203A
Page 1: ...Vector control inverter Operating manual CA Series www tpg tw com...
Page 61: ...1 TPG Corp TPG Corp 1 1 1 1 1 1 1 1 1 2 1 2...
Page 62: ...2 1 2 U V W EMC P RB R S T U V W 3 U V W AC36V 1 3 1 500V 5M 2 3 0Hz 400Hz 50Hz 4 5 PWM...
Page 70: ...18 4 7 CA Series K1 K1 K1 R S T MC1 MC2 MC1 MC2 M 3 4 5 19 4 8 4 6 R S T...
Page 101: ...80 7 1 3 7 3 81 8 1 6 LED OLED 2 1 R S T U V W IGBT 8 2...
Page 109: ...MODBUS 05H 06H 07H 08H EPPROM...